cellar, exterior) to the bottom side of the fire-
place. In case convection air is supplied (directly
or indirectly) from outside, it may also be useful
as a supply of fresh air for combustion.
At any rate, assure proper home air manage-
ment and sufficient air supply into the room.
Ensure not to use other air-consuming appli-
ances, such as heaters, cooking hoods, bath-
room ventilators, in the same room or in the
house while the stove is burning; or make sure
to have an extra ventilation grille installed for
these appliances.

3.1.3. Floor, walls

Combustible material must be sufficiently pro-
tected. The floor under the fireplace and the
walls around it must not contain electric wires.
The appliance shall be installed on floors with
an adequate load-bearing capacity.
Under the appliance
Under the appliance, any combustible material must be removed or specially
shielded by means of a 6 cm concrete slab and 10 cm insulation.
Floor round the appliance
A floor made of combustible material must be properly shielded in the following
areas:
Front: height of the lower part of the fire chamber + 30 cm, but 60 cm at least.
Sides: height of the lower part of the fire chamber + 20 cm, but 40 cm at least.
Walls, ceiling
Combustible walls behind, next to, or above the fireplace must be shielded with at
least a 10 cm stone or brick wall and 10 cm insulation. Fireproof materials should be
covered with at least 6 cm insulation.
1900
V > H + 30 > 60
S > H + 20 > 40
32
03.27831.100