Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Convection air may be led to arrive from both
the room and outside (other room, cellar, exte-
rior) to the bottom side of the fireplace. In case
convection air is supplied (directly or indirectly)
from outside, it may also be useful as a supply
of fresh air for combustion.
At any rate, assure proper home air manage-
ment and sufficient air supply into the room.
Ensure not to use other air-consuming applianc-
es, such as heaters, cooking hoods, bathroom
ventilators, in the same room or in the house
while the stove is burning; or make sure to have
an extra ventilation grille installed for these
appliances.

3.1.3. Floor, walls

Combustible material must be sufficiently pro-
tected. The floor under the fireplace and the
walls around it must not contain electric wires.
The appliance shall be installed on floors with
an adequate load-bearing capacity.
Under the appliance
Under the appliance, any combustible material must be removed or specially shield-
ed by means of a 6 cm concrete slab and 10 cm insulation. The legs of the appli-
ance may rest directly on the concrete slab and insulation must be applied inbe-
tween the legs.
Floor round the appliance
A floor made of combustible material must be properly shielded in the following
areas:
Front: height of the lower part of the fire chamber + 30 cm, but 60 cm at least.
Sides: height of the lower part of the fire chamber + 20 cm, but 40 cm at least.
Walls, ceiling
Combustible walls behind, next to, or above the fireplace must be shielded with at
least a 10 cm stone or brick wall and 10 cm insulation. Fireproof materials should be
covered with at least 6 cm insulation.
2000CB
V > H + 30 > 60
S > H + 20 > 40
31
03.27997.000

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

2000cbbs

Table des Matières