Wilo Control EC-Fire Notice De Montage Et De Mise En Service page 74

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
Holding
Name
register
40014
Bus command timer
(13)
40026
Current value
(25)
40027
Active setpoint value
(26)
40041
Pump 1 mode
(40)
40042
Pump 2 mode
(41)
40043
Pump 3 mode
(42)
40062
Switch box state
(61)
40139 –
Error state
40140
(138 – 139)
40141
Acknowledge
(140)
40142
Alarm history index
(141)
40143
Alarm history error code
(142)
64
Data type
Scale
Elements
& unit
ENUM
0. -
1. Off
2. Set
3. Active
4. Reset
5. Manual
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1 cm
1 min
0.1 h
0.1 psi
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1/day
1/month
0.1 psi
ENUM
0. Off
1. Hand
2. Auto
ENUM
0. Off
1. Hand
2. Auto
ENUM
0. Off
1. Hand
2. Auto
BITMAP
0: SBM
1: SSM
BITMAP32
0: Sensor error
1: P man
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6 Alarm
11: -
12: -
13: Frost
14: Battery Low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave communication
20: Net supply
21: Leakage
BOOL
UINT16
UINT16
0.1
Access
Added
RW
31.000
R
31.000
RW
31.000
R (dp-v)
R (dT-v)
RW
31.000
RW
31.000
RW
31.000
R
31.000
R
31.000
W
31.000
RW
31.000
R
31.000
WILO SE 06/2018