Wilo Control EC-Fire Notice De Montage Et De Mise En Service page 61

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Menu no. /
Description
4.31
Actual current of pump 3 [in A]; display changes
between L1, L2 and L3
5.02
Number of pumps
Value range: 1 ... 3
Factory setting: 2
5.06
Sensor type for pressure detection
Values: Senso, digi
Factory setting: Senso
5.08
Sensor type for volume flow detection
Values: Senso, digi, none
Factory setting: digi
5.11
Pressure sensor measurement range
Value range: 1 ... 16 bar
Factory setting: 16 bar
5.13
Volume flow sensor measurement range
Value range: 1 ... 600 m³/h
Factory setting: 60 m³/h
5.19
Zero-flow cut-off
Value range: 0 ... 60 m³/h*
Factory setting: 3 m³/h
5.40
Switching pump kick on/off
Values: off, on
Factory setting: on
Installation and operating instructions Wilo-Control EC-Fire
Menu 5.00: Installation
Display
English
51

Publicité

Table des Matières
loading

Table des Matières