baltur BT 320 Guide Rapide page 94

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

D1
D2
450
0
451
ucRelay
460
uiFaultParam
461
uiFaultParam
500
0
501
0
502
0
503
0
504
0
505
0
510
ulI2CStat
600
sSRCtrl.uiOffset
610
(ulong32)pucDst
620
(ulong32)puiDst
630
(ulong32)pulDst
700
0
701
sSelftest.sMngr.eState
710
sSelftest.sWD.eErrorState
711
sSelftest.sWD.eState
720
Selftest.sVM.ucTest2Perform
721
Selftest.sVM.eErrorState
722
Selftest.sVM.eState
730
sSelftest.sRR.eErrorState
731
sSelftest.sRR.eState
740
sSelftest.sRPW.eErrorState
741
sSelftest.sRPW.eState
750
0: USR-Stack, 1: IRQ-Stack
751
0
752
0
800
sWDog.ulReleasePtrn1
810
eFeedIndex
820
eTriggerCtrl
830
0
900
uiErrorCode
920
0
930
uiMaskedFaultCode
1200
0
1210
sIFD.eTestState
1220
sIFD.uiClock
1221
sIFD.uiClock
1222
sIFD.uiClock
1240
0
1250
uiADValue
1260
sLDR.eTestState
1270
sLDR.uiClock
1271
sLDR.uiClock
Main power relay (k2) does not switch correctly to off when out of power.
Relay does not switch correctly, when relay power is enabled (for details see enum
teRelais)
Failure of relais power switching or readback of relay coils of k1 or k2Param2: Bit 0 is
set if readback line of k1 is erroneous, Bit 1 is set if readback line of k2 is erroneous
Readback status of relay k1 or k2 differs from desired switching status, relay propably
defect.Param2:Bit 0: nominal state of k1Bit 1: nominal state of k2Bit 8: state of readback
line of k1Bit 9: state of readback line of k2
Timeout while waiting for end of write cycle
SLA+W has been transmitted; NO ACk has been received
SLA+R has been transmitted; NO ACk has been received
Data byte has been transmitted; NO ACk has been received
BUS error due to an illegal START or STOP condition
Arbitration lost in SLA+R/W or Data bytes
Unknown/invalid state!
Correction of defective triple in Safety RAM structure failed
Invalid destination address
Invalid destination address
Invalid destination address
CPU selftest failed
state-event-machine failed with AC_ERR
Watchdog selftest failed
Invalid default case
Invalid default case
Supply voltage monitor selftest failed
Invalid default case
Relay release circuit selftest failed
Invalid default case
Relay PWR release circuit selftest failed
Invalid default case
Stack overflow detected
Stackaddress is NULL-Pointer
Stackaddress is NULL-Pointer
Trigger release patterns are invalid!
Invalid Feed Index
Invalid Trigger Mode
No valid watchdog trigger received (frequency or duty cycle invalid)
Fault from LPC_API error handler
Invalid entry in iStoerResRam
uiMaskedFaultCode out of range!
Flame signal doesn't disappear during self-test
Invalid default case
UP is missing test impulses
Test signal duration too short
Test signal duration too short
Detected short circuit of LDR
Circuit selftest failed, A/D value out of expected range
Invalid default case
Test interval too long
HP released test pin too late
42 / 50
0006081511_201311
Description

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Bt 330Bt 340

Table des Matières