Safety Instructions; Technical Data - Eaton CROUSE-HINDS EXIT N Série Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1.
Legende
Warning
This symbol warns of a serious hazard.
Failure to observe this warning may result
in death or the destruction of property.
Caution
This symbol warns of a possible failure.
Failure to observe this caution may result
in the total failure of the device or the
system or plant to which it is connected.

1.1 Safety instructions

For skilled electricians and
qualified personnel in accordance
with national legislation, including
the relevant standards and, where
applicable, in acc. with
IEC/EN 60079-14 on electrical apparatus for
explosive atmospheres.
– The light fitting must not be operated in
zone 0 or 20 hazardous areas!
– The technical data indicated on the light
fitting are to be observed!
– The requirements of the
EN/IEC 60079-31 regarding excessive
dust deposits and temperature to be
considered from the user.
– Changes of the design and modifications
to the light fitting are not permitted!
– The light fitting shall be operated as
intended and only in undamaged and
perfect condition!
– Do not keep these operating instructions
inside the light fitting during operation!
The national safety rules and regulations
for pre vention of accidents and the
following safety in structions which are
marked with an ( ) in these operating
instruction, will have to be observed!
10
Explosion protected LED­exit luminaire
Series: EXIT N
2.

Technical data

EU­Type Examination Certificate:
Marking acc. to 2014/34/EU and and standard of series
EN 60079
IECEx Certificate of Conformity:
Category of application standard of series
IEC 60079
Rated voltage:
* the data consider an additional voltage tolerance of ± 10 %
Rated frequency:
Rated current:
Battery:
Charging time:
Duration of emergency lighting:
** Note: New batteries will reach their total useful capacity only after 3 charging/discharging cycles
Insulation class to IEC/EN 61140:
Degree of protection accd. IEC/EN 60529:
Operation temperature:
Storage temperature in original packing:
Weight:
Supply terminal clamping capacity
Ex e / Ex t cable entry M20x1.5
suitable cables and test torques of the pressure screw Ø cable (mm)
Seal 1+2+3:
1 2
3
Seal 1+2:
1 2
3
Seal 1
1 2
3
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance work
on the cable entry.
metal:
Test torque flange for Ex e / Ex t cable entry
M20x1.5:
Test torque for mounting screws cover:
BVS 09 ATEX E 029
ta max + 40 °C:
II 2 G Ex eb ib mb IIC T5 Gb
ta max + 50 °C:
II 2 G Ex eb ib mb IIC T4 Gb
II 2 D Ex tb IIIC T80 °C Db
IECEx BVS 13.0017
ta max + 40 °C:
Ex eb ib mb IIC T5 Gb
ta max + 50 °C:
Ex eb ib mb IIC T4 Gb
Ex tb IIIC T80 °C Db
AC:
110 ­ 277 V *
DC:
110 ­ 250 V *
50 ­ 60 Hz
110 V AC/DC:
approx. 0.06 A
220 V AC/DC:
approx. 0.035 A
Accu 2 x 6 V/ 0.8 Ah
28 h
3 h **
I
IP 66
­20 °C ... +40 °C /+50 °C
specified data:
+5 °C ... +35 °C
­20 °C ... +50 °C
approx. 2.5 kg
2x per terminal:
3 x 2.5 mm²
min.
5.5
(1))
max.
7 .0
min.
7 .0
(1)
max.
9.0
min.
9.5
(1)
max.
13.0
M20x1.5 thread
2.7 Nm
2.4 Nm
GB
Nm
1.5
1.0
1.5
1.4
1.0
1.7

Publicité