2.2.1 Periodical transmission with or without historisation

The product enables to measure and send the data from the probe following the diagram bellow.
This periodical transmission can be done with or without historisation of the data.
The product enables to activate or deactivate a probe. The 0x57 frame will be different depending if 1 or 2 probes are activated.
Parameters associated to this mode are:
• Sampling period (register S321), historisation frequency (register S320) and transmission frequency (register S301)
• Activation of the probes (register S324).
Stand-by mode
Sampling peri-
od reached?
Temperature
measure and saving
probe 1
Temperature
measure and saving
probe 2
Historisation
frequency
reached?
Transmission
frequency
reached?
Sending 0x57
Example without historisation:
No
In this example:
Yes
Example with historisation:
No
Yes
In this example:
No
Yes
Register Encoding
Value
S321
Decimal
1800
S320
Decimal
1
S301
Decimal
1
S324
Decimal
3
• 1 sample (reading) every hour (1800 x 2 seconds = 60 minutes)
• 1 historisation at each sample and the frame is sent immediately (so every
hour)
• The 2 probes are activated so the product will read the temperature on the 2
probes every hour.
Register Encoding
Value
S321
Decimal
1800
S320
Decimal
1
S301
Decimal
2
S324
Decimal
3
• A sample (reading) every hour (1800x2secondes = 60 minutes)
• An historisation done at each sampling (so every hours)
• A transmission is done every 2 historisations (so every 2 hours, so 12 times a
day)
• The 2 probes are activated so the product will read the temperature on the 2
probes every hour.
Result
1 sample every hour
(1800 x 2 seconds = 60 minutes)
1 historisation for each sample
1 transmission for each historisation
The 2 probes are activated
Result
1 sample every hour
(1800 x 2 seconds = 60 minutes)
1 historisation for each sample
1 transmission every 2 historisations
The 2 probes are activated