2.2.2 Periodical transmission with redundancy

The product enables to add redundancy in the frame sent (cf diagram bellow). Thanks to the redundancy the product will save samples locally in
order to resend them in the next frame.
Parameters associated to this mode:
• Sampling period (register 321), historisation frequency (register 320) and transmission frequency (register 301)
FR
• Activation of the probes (register 324).
• Number of samples to be repeated from a frame to another (register 323).
When redundancy is activated, the frame will contain the number of bytes corresponding to the total number of samples, so S301+S323. At the
start-up of the product, bytes assigned to the redundant samples will be filled with zeros as long as there is no memorized samples.
Example with redundancy:
EN
Register Encoding
S321
Decimal
S320
Decimal
S301
Decimal
S324
Decimal
S323
Decimal
In this example:
• A sample (reading) every hours (1800 x 2 seconds = 60 minutes)
• A historisation at each sampling
• A transmission done every 2 historisations (so every 2 hours)
• 2 probes are activated
• The product will send 2 new samples measured every hour and 1 memorized sample.
Frame 1
Frame 2
Frame 3
Frame 4
Frame 5
Frame 6
Frame 7
New samples
Samples memorized
Value
Result
A sample every hour
1800
(1800 x 2 seconds = 60 minutes)
1
1 historisation at each sampling
2
1 transmission every 2 historisations
3
The 2 probes are activated
1
1 sample repeated in each frame
Historisation/
Saving
Transmission
1h
2h
3h
4h
5h
6h
7h
8h
9h 10h 11h 12h 13h 14h 15h
Time
48 of 57