English
10.6
Minimum room temperature
This function can be used to ensure that a minimum
room temperature is specified even during OFF times,
for example in timer mode (week program).
NOTE
The specification also applies for the runback timer
function. Frost protection mode has priority.
Press and hold the MENU key and the FORWARD
key for five seconds. rb display flashes.
Press the
key The display Sb flashes.
Press the ENTER key. The ON symbol flashes.
Press the ENTER key. The minimum room
temperature (factory setting 16° C) flashes.
Use
or
to set the minimum room
temperature and confirm with ENTER.
Confirm the BACK key to return to the standard
display.
EN-8
10.7
Adaptive start-up
This function guarantees that the set room
temperature is reached precisely at the start of the
switch-on time, e.g. in conjunction with a time
program.
Example:
In the timer menu, a set room temperature of 22°C is
specified. The current room temperature is 17° C. The
heating device switches on early so that the specified
room temperature of 22° C is reached by 07:00.
Press and hold the MENU key and the FORWARD
key for five seconds.
rb display flashes.
Press
or
symbol. The symbol flashes.
Press the ENTER key.
Press
or
function on or off.
Confirm the BACK key to return to the standard
display.
2208/D
MFP 100E - MFP 200E
to select the ADAPTIVE START
to select ON or OFF to switch the
www.dimplex.eu