4.5 Remote control

The AQ Logic remote control system can be operated using an
external or an internal voltage supply.
The input circuits are fully opto-isolated. The self-hold pulse
command system requires 4 connecting wires on the client terminal
strip: Common, STOP, OPEN and CLOSE. If the STOP push-button is
not used, do not connect the STOP wire, OPEN (or CLOSE) contact
must be maintained to operate the actuator.
These commands are self-holding (pulse commands) as a standard.
To remove self-holding, remove wire to terminal 7.
4.5.1

Dry contact control

A jumper must be fitted across customer terminal 9-10.
4.5.2

Voltage control

Remote control can use either in AC or DC voltage.
!
Never connect voltage sources above 60V on common terminal 5.
English
S - Stop
C - Close
O - Open
S - Stop
C - Close
O - Open
Use terminal 10 for voltage from 10 to 60V.
Use terminal 11 for voltage from 90 to 250V.
19