Assembling The Appliance; Commissioning; Initial Start-Up - Stiebel Eltron SHP-F 220 Premium Utilisation Et Installation

Masquer les pouces Voir aussi pour SHP-F 220 Premium:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALLATION

Commissioning

10.6 Assembling the appliance

Note
f Refit the appliance cover after completing your
f
work. See chapter "Maintenance and cleaning / Fit-
ting the appliance cover").
11. Commissioning
WARNING Electrocution
Never operate the appliance when the casing is open,
without a cover or without side air connectors.

11.1 Initial start-up

Note
Fill the DHW cylinder before switching on the power
supply to the appliance. The appliance is equipped with
boil-dry protection to prevent operation with an empty
DHW cylinder.
Note
Following an interruption of the power supply, the
compressor operation remains blocked for at least one
minute. The PCB delays electronic starting by a minute,
during which the appliance goes through its initialising
process. If the compressor subsequently fails to start, it
may be locked out by additional safety devices (motor
overload relay or high pressure switch). This block should
lift after 1 to 10 minutes.
Fan graph with examples showing how to calculate the necessary fan setting with a duct connection
65
60
55
50
45
40
35
0
10
X Pressure drop [Pa]
Y Fan setting [%]
24
| SHP-F 220-300 Premium
20
30
40
Example 2
11.1.1 Fan setting subject to pressure drop
The appliance requires a constant air flow rate of 350 m³/h to op-
erate correctly. If an air duct is connected, the fan output must be
adjusted in the appliance menu due to the resulting pressure drop.
The factory setting is 40 %, intended for recirculation air mode.
Standard system with 5 m air duct (DN 160) and two 90° bends
Length or
Folded spiral-seam tube
90° bend (r = 1 * d)
Intake grille
Total
f Set the fan output to 47 % in the control unit menu.
f
Standard system with 5 m air duct (DN 200) and two 90° bends
Length or
Folded spiral-seam tube
90° bend (r = 1 * d)
Intake grille
Total
f Set the fan output to 44 % in the controller menu.
f
Note
If the air duct is longer or there are more bends, perform
the following individual system calculation.
50
60
70
Example 1
1 Fan curve
Pressure drop per
Pressure
pce
m or per pce [Pa]
drop [Pa]
5
2
2
5.5
2
6.2
Pressure drop per
Pressure
pce
m or per pce [Pa]
drop [Pa]
5
0.67
2
2.3
2
6.2
80
90
www.stiebel-eltron.com
10
11
12.4
33.4
3.35
4.6
12.4
20.35
1
100