OPERATION
Settings
The tHE0 setting disables the "runt-
ime-dependent rapid heat-up" function.
This function is enabled via setting tHE1.
The function is disabled at the factory.
Switch between the tHE0 and tHE1 set-
tings using the "Plus" and "Minus" keys.
The tHE1 setting allows the electric
emergency/booster heater to cut in if
the set temperature is not reached after
expiry of the runtime selected below.
Time input for the "runtime-dependent rapid heat-up"

function
Set the runtime using the "Plus" and
"Minus" keys. After the set number of
hours, the appliance checks whether the
set temperature has been reached. If this
is not the case, the appliance switches on
the electric emergency/booster heater.
The factory default is 8 hours.
t
thE0
thE1
tE08
1 Heat pump symbol
2 Electric emergency/booster heater symbol
tHE0 Runtime-dependent rapid heat-up disabled
tHE1 Runtime-dependent rapid heat-up enabled
tE08 Adjustable number of hours (e.g. 8 in this case) during
which heating is only provided by the heat pump

Changing units
You can select whether the temperatures and the volume details
are displayed in SI units or US units. If you select 1, the values are
displayed in degrees Celsius and litres. If you select 0, the values
are displayed in degrees Fahrenheit and gallons.
Press the "Menu" key until "SI" appears
in the display.
Using the "Plus" and "Minus" keys, set
whether the display should use SI units
(1) or US units (0).
www.stiebel-eltron.com

See chapter "Troubleshooting / Fault codes".

A fault code preceded by E appears if the fault relates to the re-
frigerant circuit. Notify a qualified contractor.
4.3
4.3.1 Quick/comfort heat-up
Normally, the "Rapid heat-up" key is used to enable rapid/comfort
heating, which enables you to cover unexpectedly high DHW de-
mands without changing any of the appliance's standard settings.
If quick/comfort heat-up is activated manually by pressing the
relevant key, the heat pump and the electric emergency/boost-
er heater will start in parallel, irrespective of the selected set
temperature, and will remain active until the DHW temperature
in the cylinder has reached 65 °C. To save energy, the electric
emergency/booster heater switches off early, as soon as a tem-
1
perature of 65 °C has been achieved in the upper cylinder section
(quick heat-up). The rapid/comfort heating function remains active
2
until a temperature of 65 °C has been achieved throughout the
DHW cylinder (comfort heating). The appliance then automatically
switches back to the previously set parameters.
Fault code
If the "Service/fault" symbol illuminates
or flashes, you can query the fault code
using the "Menu" key. This menu remains
disabled if no fault has arisen.
E fault code

"Quick heat-up" key

Press the "Quick heat-up" key.
The "heat pump" and "electric emergen-
cy/booster heater" symbols appear.
Note
The "electric emergency/booster heater" and "heat pump"
symbols are displayed until the rapid/comfort heating
terminates.
During rapid/comfort heating, the "electric emergency/
booster heater" symbol is displayed until the heat pump
has heated the entire cylinder content to 65 °C and the
function terminates. The electric emergency/booster
heater already switches off when the 65 °C has been
achieved in the upper cylinder section.
Note
If the quick/comfort heat-up has been activated unin-
tentionally, you can cancel the function by lowering the
set temperature.
f Hold down the "Minus" key, until you hear a clicking
f
noise caused by the heat pump and emergency/
booster heater switching off. At the same time, the
set temperature also reverts to the value that was
selected before quick/comfort heat-up was enabled.
SHP-F 220-300 Premium |
11