Télécharger Imprimer la page

Dräger Polytron 6100 EC WL Notice D'utilisation page 41

Masquer les pouces Voir aussi pour Polytron 6100 EC WL:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 54
See technical manual "Wireless Communication ISA100-Wireless
91 00 000, download at www.draeger.com/ifu) for information on:
Recommended network components
Creating the provisioning file (see also the PolySoftHTML help pages)
8.2
Signal transmission to the controller
Publication Rate: 1x every 10 seconds (Yokogawa Management Station)
8.3
ISA100 Wireless
The gas detector outputs ISA100 Wireless
Display
Access
PV
READ
PV
READ
PV
READ
PV
READ
PV
READ
DIAG_STATUS
READ
DIAG_STATUS
READ
DIAG_STATUS
READ
DIAG_STATUS
READ
For further information see: "Troubleshooting", page 44.
8.4
Repeater feature
The feature can be enabled or disabled as part of the network integration. For
gas detector energy optimization, disabling the feature is recommended when
there is no need for it due to the network topology.
Instructions for use
|
Dräger Polytron
TM
" (order no.
standard objects
standard objects with attributes for process values (PV) and diagnosis status (DIAG_STATUS) and PROFIsafe data.
Byte no.
1
2
3
4
5
1
2
3
4
®
6100 EC WL, Dräger Polytron
Measured value updates (publication rate) and timeout times can be set via
the Yokogawa infrastructure.
If there is no sample gas, the gas detector only outputs data every other time
window (power-save mode). If sample gas is present in sufficient concentration,
all time windows are used.
Content
Modbus input register
PV_Status
Register N
PV_Value (1/4)
Register N+1
PV_Value (2/4)
PV_Value (3/4)
Register N+2
PV_Value (4/4)
Diag_Status (1/4)
Register M
Diag_Status (2/4)
Diag_Status (3/4)
Register M+1
Diag_Status (4/4)
®
Repeater ISA100
|
en
Network integration
Data type
UINT (16 bit)
32-bit float (4 bytes),
Float32 acc. to IEEE 754
UINT (16 bit)
UINT (16 bit)
41

Publicité

loading

Ce manuel est également adapté pour:

Polytron isa100