4.2.5
Connecting the ISA100 Wireless
®
● Connect Windows
end device to the respective management station of the
ISA100 Wireless
network.
The configuration is done with PolySoft.
5
Mechanical installation
WARNING
Risk of explosion!
In explosion-hazard areas, electrostatic discharge may cause a spark to ignite
on the antenna.
► Do not install the antenna in explosion-hazard areas subject to intense
electrostatic charging, for example, due to fast moving particles or
pneumatic transport of powders.
WARNING
Risk of explosion!
In explosion-hazard areas, electrostatic discharge may cause a spark to ignite
on the housing and sensing head.
► Do not install the gas detector in dust explosion-hazard areas subject to
intense electrostatic charging, for example, due to fast moving particles or
pneumatic transport of powders.
5.1
Installing the gas detector - installation
without mounting accessories
The gas meter is installed vertically on a flat surface with the antenna facing
upwards.
For installation with mounting accessories, see corresponding assembly
instructions.
Prerequisites:
A suitable installation location is selected (see "Safety information", section
"Mechanical installation", page 32).
Instructions for use
|
Dräger Polytron
interface
®
6100 EC WL, Dräger Polytron
CAUTION
Risk of explosion!
The gas detector is not tested in environments with increased oxygen content
(> 21 % O
).
2
► Do not use the gas detector in environments with increased oxygen content.
Install the gas detector:
● Install the gas detector using the drilling template (see appendix "Drilling
template") and M6 (1/4") hexagon socket head cap screws.
5.2
Installing the antenna
1. Remove the cover cap from the antenna connector (Fig. A 4).
2. Screw the antenna into the connector and tighten it by hand.
5.3
Installing the remote antenna
1. Remove the protective cap for the antenna on the connection (Fig. A 4).
2. Screw antenna cable to connection and tighten hand-tight.
3. Select an installation location where a perfect signal transmission is
ensured. The antenna must point up vertically.
4. Attach the mounting bracket at the installation location of the remote
antenna.
5. Lay the antenna cable.
6. Screw the remote antenna in at the end of the antenna cable and tighten it
by hand.
5.4
Installing the EC sensor
Prerequisites:
The gas detector is installed.
If the gas detector is already switched on and an existing sensor is changed,
see "Replacing the sensor", page 49.
Install sensor:
1. Loosen the set screw (Fig. B 2).
2. Unscrew the bayonet ring (Fig. B 3).
®