Wiring Diagram - Toshiba RBC-TRP100E Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Branch Kit 1:3
 Wiring Diagram
Remote
Controller
Header
A
Indoor
Unit
1
2
E
Outdoor
1
2
Unit
L
N
Power supply
<RAV-SM1603AT-E>
REQUIREMENT
The remote controller wiring has no polarity. Connections to terminals A and B of an
indoor unit may be replaced with each other.
The remote controller wires and power supply wire must not be in direct contact or in the
same conduit pipe. (Doing so may cause a malfunction of the control system due to
noise.)
 Wiring Specification
Specification of Wires Between Units and Numbers of Wires.
Outdoor unit - indoor unit
(header unit)
Indoor unit
- indoor unit
(header unit)
(follower unit)
Remote controller wiring
Earth wire of indoor unit
Procure necessary parts and perform all connection work locally.
EN
Follower
B
Indoor
Unit
3
H
F
3
<RAV-SP1604AT8, SM224*AT8, SM280*AT8 series>
No. of wires
Wire diameter
No. of wires
Wire diameter
No. of wires
Wire diameter
A
B
1
2
3
1
2
3
L1 L2 L3
N
Power supply
H07RN-F or 60245IEC66 1.5 mm
H07RN-F or 60245IEC66 1.5 mm
Between 0.5 mm
H07RN-F or 60245IEC66 1.5 mm
15
Follower
A
Indoor
Unit
1
2
H
4 (Include earth wire)
2
2 (Shield wire)
2
2
and 2 mm
(up to 200 m)
G
B
3
H
2
or more
2
or more
2
or more