Wiring Diagram - Toshiba RBC-DTWP101E Manuel D'installation

Branch kit set 1:4
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Branch Kit Set 1:4

Wiring Diagram

Remote controller
Remote controller
wiring
Indoor side
Indoor/Outdoor
connecting
wires
Outdoor side
Power supply
REQUIREMENT
The remote controller wiring has no polarity. Connections to terminals A and B of an
indoor unit may be replaced with each other.
The remote controller wires and indoor-indoor connecting wire must not be in direct
contact or in the same conduit pipe. (Doing so may cause a malfunction of the control
system due to noise.)
Wiring Specification
Specification of Wires Between Units and Numbers of Wires.
Outdoor unit - indoor unit
(header unit)
Indoor unit
- indoor unit
(header unit)
(follower unit)
Remote controller wiring
Earth wire of indoor unit
Procure necessary parts and perform all connection work locally.
A B
1
2
3
1
2
3
L1 L2
L3
N
No. of wires
Wire diameter
No. of wires
Wire diameter
No. of wires
Wire diameter
A B
A B
1
2
3
1
3 (Include earth wire)
H07RN-F or 60245IEC66 1.5 mm
H07RN-F or 60245IEC66 1.5 mm
Between 0.5 mm
H07RN-F or 60245IEC66 1.5 mm
12
A B
2
3
1
2
or more
2
2
or more
2 (Shield wire)
2
2
and 2 mm
(up to 200 m)
2
or more
2
3