Toshiba RBC-TRP100E Manuel D'installation page 7

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Branch Kit 1:3
<RAV-GM224*AT8, GM280*AT8 series>
Indoor unit C
Pipe length
(one way)
Refrigerant
pipe
specifications
Height
difference
*1: Full length of the following model is 50 m.
RAV-GM2241AT8(J)-E, RAV-GM2241AT8(J)-TR,
RAV-GM2801AT8(J)-E, RAV-GM2801AT8(J)-TR
CAUTION
When planning a layout for Units A, B and C, comply with the following:
1. The lengths after branching ("a" and "b", "b" and "c", "a" and "c") should be equal if
feasible. Install Units A, B and C so that the difference of the branching lengths becomes
less than 10 m if the lengths cannot be equal due to the branch pipe position.
2. Install Units A, B and C on the same level. If Units A, B and C cannot be installed on the
same level, the difference in level should be limited to 0.5 m or less.
Indoor unit B
b
Branch pipe
c
L
Main pipe
Total length (L + a, L + b, L + c)
Branch pipe length (a, b, c)
Maximum difference between indoor units
(|a - b|, |b - c|, |c - a|)
Between indoor units (Δh)
Between indoor
unit and outdoor
unit
Indoor unit A
Branch pipe
Branch pipe
a
Distributor
When outdoor unit is higher (H)
When outdoor unit is lower (H)
6
H
EN
1
100*
m
20 m
10 m
0.5 m
30 m
30 m
EN

Publicité

Chapitres

Table des Matières
loading

Table des Matières