Toshiba RBC-TRP100E Manuel D'installation page 12

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Branch Kit 1:3
<RAV-SM2246AT8, SM2806AT8 series>
Indoor unit C
Formula for Calculating Additional Refrigerant Amount
Do not remove the refrigerant even if the additional refrigerant amount becomes minus
result as a result of calculations by the following formula and operate the air conditioner as it
is.
Additional refrigerant amount (kg) = Main piping additional refrigerant amount (kg) +
α:
Additional refrigerant amount per meter of actual main piping length (kg)
γ:
Additional refrigerant amount per meter of actual branch piping length (kg)
L:
Actual length of main piping (m)
a, b, c: Actual length of branch piping (m)
L
SM2246
Ø12.7
SM2806
CAUTION
1. Be certain to write the additional refrigerant amount, pipe length (actual length), head
and other specification on the nameplate put on the outdoor unit for recording.
2. Seal the correct amount of additional refrigerant in the system.
EN
Branch pipe
c
L
Main pipe
Branch piping additional refrigerant amount (kg)
= {α × (L – 28)} + {γ × (a + b + c – 6)}
Connecting pipe diameter
(Liquid side)
a
b
Ø9.5
Ø9.5
Indoor unit B
Branch pipe
b
Branch pipe
Distributor
Additional refrigerant amount per
c
Ø9.5
11
Indoor unit A
a
Meter (kg/m)
α
β
0.090
H
γ
0.045

Publicité

Chapitres

Table des Matières
loading

Table des Matières