Reset Procedure; Actuator Limit Stop - GIESSE RACK MAX 650 Manuel D'utilisation Et D'installation

Masquer les pouces Voir aussi pour RACK MAX 650:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 85
IMPORTANT. If the TUBE LOCK electromechanical lock is connected to only one
actuator, a fresh R
Before starting the R
connection with the TUBE LOCK.

Reset Procedure

12.1.
This procedure is used to configure a single actuator, configure a set of synchronizable
models or with electromechanical TUBE LOCK.
IMPORTANT. The dip-switch must be set with the actuators not powered. After
each modification wait a few seconds (~5 s) before powering the actuator again
in order to make it effective.
▪ Set the dip-switch to OFF. With multi-device configuration (or with TUBE LOCK
electromechanical lock) where G
must be performed only for one actuator, the other devices will be associated
automatically.
▪ Power up the actuators (it does not matter whether they are in the open or closed
position). The initialization phase has begun. The actuator starts moving at once
about 8 seconds if a TUBE LOCK lock is installed)
completely retracted) and then moves about 5 cm in the opening direction. During this
phase, make sure that there are no obstructions impeding movement of the rack and
wait for all machines to complete the procesure in the case of synchronized actuators.
▪ On completion of the operation, each connected machine will flash an orange light to
indicate the end of the R
device, indicating the address acquired (actuator 1 → 1 flash → pause → 1 flash →
pause; actuator 2 → 2 flashes → pause → 2 flashes → pause, and so on).
▪ The power supply to the machines can now be turned off.
▪ The opening stroke
or it can be customized at will; this is decided at this step.
▪ Operate the actuator in O
desired position (stroke customization). The instant you remove power, that will be the
extended limit stop position. This extended position will be stored and used as stroke
limit when O
synchronously and stop at the same position.
▪ In case the opening is not at the desired position, the R
For operations to be carried out on the electromechanical TUBE LOCK lock, refer
to the relative use and installation manual.

Actuator limit stop

12.2.
The opening and closing limit stop position is automatic and cannot be programmed. The
actuator stops as a result of the power absorption that the actuator undergoes when the rack
(on the way out) reaches its inner limit stop or (on the way back) when the door is completely
closed with the seals completely compressed, i.e. when the absorbed power exceeds a
preset threshold in the microprocessor.
procedure must be performed.
ESET
ESET
REEN
procedure. The number of flashes will be different for each
ESET
can be left as produced in the factory (maximum stroke)
(rack output)
mode without interrupting the power supply up to the
PEN
. In the case of synchronized actuators they will all move
PENING
procedure, it is suggested to verify the electrical
wires have been connected, the dip-switch setting
and performs a total closure stroke (rack
48
procedure must be repeated.
ESET
(after