Télécharger Imprimer la page

Read Immediately; Important Information; Intended Use; Legal Provisions And Guidelines - Dimplex SI 50TE Instructions D'installation Et D'utilisation

Pompe à chaleur eau glycolée-eau pour installation intérieure

Publicité

Les langues disponibles

Les langues disponibles

1
1

Read immediately

1.1 Important Information

ATTENTION!
Any work on the heat pump may only be performed by an authorised and
qualified customer service.
ATTENTION!
Devices with 3 kg refrigerant or more must be leak-proof tested yearly
according to (EC) No. 842/2006.
ATTENTION!
The heat pump must not be tilted more than max. 45° (in either direction).
ATTENTION!
The transport securing devices must be removed prior to commissioning.
ATTENTION!
The heating system must be flushed prior to connecting the heat pump.
ATTENTION!
The supplied strainer must be fitted in the heat source inlet of the heat
pump in order to protect the evaporator against the ingress of impurities.
ATTENTION!
The brine solution must contain at least 25 % of an antifreeze agent on a
mono-ethylene glycol or propylene glycol basis and must be mixed prior
to filling.
ATTENTION!
The clockwise phase sequence must be observed when connecting the
load lines (the heat pump will deliver no output and will be very noisy
when the phase sequence is incorrect).
ATTENTION!
Commissioning is to be effected in accordance with the installation and
operating manual of the heat pump manager.
ATTENTION!
To prevent the accumulation of deposits (e.g. rust) we recommend using
a suitable corrosion protection system.
ATTENTION!
Disconnect all electrical circuits from the power supply before opening
the enclosure.

1.2 Intended Use

This device is only intended for use as specified by the manufac-
turer. Any other use beyond that intended by the manufacturer is
prohibited. This requires the user to abide by the manufacturers
product information. Please refrain from tampering with or alter-
ing the device.
EN-2
All manuals and user guides at all-guides.com
1.3 Legal Provisions and
This heat pump is designed for use in a domestic environment
according to Article 1, Paragraph 2 k) of EC directive 2006/42/EC
(machinery directive) and is thus subject to the requirements of
EC directive 2006/95/EC (low-voltage directive). It is thus also in-
tended for use by non-professionals for heating shops, offices
and other similar working environments, in agricultural establish-
ments and in hotels, guest houses and similar / other residential
buildings.
This heat pump conforms to all relevant DIN/VDE regulations
and EU directives. For details refer to the EC Declaration of Con-
formity in the appendix.
The electrical connection of the heat pump must be performed
according to and conforming with all relevant VDE, EN and IEC
standards. Beyond that, the connection requirements of the local
utility companies have to be observed.
The heat pump is to be connected to the heat source and heat
distribution systems in accord-ance with all applicable provi-
sions.
Persons, especially children, who are not capable of operating
the device safely due to their physical, sensory or mental abilities
or due to their inexperience or lack of knowledge, must not oper-
ate this device without supervision or instruction by the person in
charge.
Children must be supervised to ensure that they do not play with
the device.
Any work on the heat pump may only be performed by an authorised and
qualified customer service.
Devices with 3 kg refrigerant or more must be leak-proof tested yearly
according to (EC) No. 842/2006.
More information is available in the chapter Care / Cleaning.
1.4 Energy-Efficient Use of the
By operating this heat pump you contribute to the protection of
our environment. A prerequisite for an efficient operation is the
proper design and sizing of the heating system and the heat
source system. In particular, it is important to keep water flow
temperatures as low as possible. All energy consumers con-
nected should therefore be suitable for low flow temperatures. A
1 K higher heating water temperature corresponds to an in-
crease in power consumption of approx. 2.5 %. Low-temperature
heating systems with flow temperatures between 30 °C and
50 °C are optimally suited for energy-efficient operation.
Guidelines
ATTENTION!
ATTENTION!
Heat Pump

Publicité

loading

Ce manuel est également adapté pour:

Si 75teSi 100teSi 130te