Technical data

Type
Supply
Power consumption
Nominal force
Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Emission sound pressure level
Nominal stroke length *
Additional functions *
* Programmable with software SCS
Running speed and forces
All forces + approx. 20 %
switch-off reserve (temporary)
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing range 3 and 2, the drive runs
"OPEN" for 10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closing range 2 and
1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
6/16
KA34/54-K-BSY+ Set
KA 34-K-BSY+ Set
230 V AC, +10 % / -15 %, 50 Hz
45 W / 75 VA
2 x 300 N
Max. 2600 N (VdS 2580: 2000 N; without bracket)
>20 000 double strokes
30 % (With cycle time 10 minutes)
Aluminium, powder-coated in ~RAL 9006
IP 32
(With covering stoppers delivered with bracket sets)
-15 ... +75 °C (VdS 2580: -5 ... +75 °C)
30 min / 300°C
LpA ≤ 70 dB(A)
See type plate
Closing edge protection activated (3 stroke repeatings);
Locking relief activated
English
KA 54-K-BSY+ Set
75 W / 115 VA
2 x 500 N
99.823.97 2.8/10/21