Technical Data

Type
Power supply
Nominal force
Nominal stroke *
Running time (OPEN)
Ingress protection
Lifetime
Duty cycle
Housing
Temperature range
Fire stability
Additional functions *
* Programmable with SCS software
Running speed and forces
Cable from
the top
CLOSED
OPEN

Maintenance and cleaning

Inspection and maintenance has to be carried out
according to D+H maintenance notes. Only original
D+H spare parts may be used. Repair is to be carried
out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.
99.823.44 2.0/11/14
LDH 800/070
24 VDC / ±15% / 0,8 A
800 N
70 mm
≤ 53 sec.
IP 50
>10 000 double strokes
30 %, With cycle time 10 minutes
Stainless steel
-5 ... +75°C
30 min / 300°C
Closing edge protection activated, 3 stroke repeatings
0,7 mm/sec.
I
5,6 mm
840 N
1,4 mm/sec.
II
24,4 mm
800 N
1,4 mm/sec.
III
800 N
English
Closing edge protection
In the "CLOSE" direction the drive has an
active protection for the main closing
edge. If there is an overload in the closing
range 3 and 2, the drive runs "OPEN" for
10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the
drive remains in this position.
Significantly greater forces
can be exerted at the
secondary closing edges.
Danger of crushing hands
and fingers!
Guarantee
You will get 2 years guarantee for all D+H products
from date of verified handing over of the system up to
maximal 3 years after date of delivery, when
mounting and starting has been carried out by an
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H
components with external systems or with mixing of
D+H products with parts of other manufacturers.