Technical data
Type
Supply
Power consumption
Nominal force
Nominal locking force
Service time
Duty cycle
Housing
Ingress protection
Temp. range
Fire stability
Emission sound pressure level LpA ≤ 70 dB(A)
Nominal stroke length* / **
Additional functions **
* Programmable with software SCS and BI-BT2 via Bluetooth
Normal operation =
SHEV- fast running =
Forces
LA 35
LA 85
OPEN
300 N
800 N
CR III
300 N
800 N
CR II
300 N
800 N
CR I
300 N
800 N
All forces + app. 20 % switch-off reserve (temporary)
Mounting informations
- The drive set will be full configured by factory.
The drives must be reconfigured in case of
alterations (e.g. removing of drives from existing
set or integrating a new drive) with SCS
- Use only drives with the same force.
- Ensure evenly load distribution on all the drives
- Eyebolt has to be adjusted so, that the drive is
disconnected with closed flap through it's inside
stop position damping. Brackets can be damaged
by to rigid adjustment!
99.950.97 1.1/04/16
LA 35-K-BSY+
230 V AC, ±10%
20 W / 30 VA
300 N
1100 N
>20 000 double strokes
30 % (with cycle time 10 minutes)
Aluminium powder-coated (~RAL 9006), polycarbonate
IP 65 ("-W" = IP 54)
-5 ... +75°C
30 min / 300°C
See type plate
Closing edge protection activated (3 stroke repeatings)
LA 105 LA 155
1000 N
1500 N
1000 N
1000 N
1000 N
1000 N
800 N
800 N
LA 85-K-BSY+
LA 105-K-BSY+
230 V AC, ±10%
230 V AC, ±10%
30W / 45 VA
35 W / 55 VA
800 N
1000 N
Running speed and forces
Shifting of drive cable
Disconnect drive from electric voltage!
English
LA 155-K-BSY+
230 V AC, ±10%
45 W / 70 VA
1500 N
LA 35-85-105-K-BSY+
5/12