Display
Error
a
1)
keypad
PC
EF
63
Communication error to
CAN-IN2
a
EF
64
Communication error to
CAN-IN1 with event or time control
a
EF
65
BUS-OFF
(many communication errors
occurred)
a
((
91
External fault (TRIP-Set)
a
a
+
105
Internal fault
PF
74
Fault in program execution
a
PJ
79
Initialisation error during transfer of
parameter set
a
a
3 
75
Internal fault
3 
72
Wrong PAR1 transfer when using
a
the keypad/PC.
3 
79
Internal fault
1)
LECOM fault number

Troubleshooting and fault elimination

MA DrivePLC DE/EN/FR 1.0
Cause
CAN-IN2-object receives faulty data
or communication is interrupted
CAN-IN1-object receives faulty data
or communication is interrupted
The Drive PLC has received too
many incorrect telegrams via the
system bus and has been
disconnected
A digital signal assigned to TRIP set
has been activated
A fault was detected in the program. Send the Drive PLC with the data
l
A fault was detected during the
transfer of the parameter set to
the Drive PLC.
l
Parameter set does not match
Drive PLC
PAR1 is defective.
Remedy
l
Ø
Plug-in connection - bus module
Check FIF
l
Check transmitter
l
Increase monitoring time under
C0357/2 if necessary
l
Ø
Plug-in connection - bus module
Check FIF
l
Check transmitter
l
Increase monitoring time under
C0357/3 if necessary
l
Check whether bus terminator
available
l
Shield control of the cables
l
Check PE connection
l
Check bus load, if necessary,
reduce the baud rate
Check external encoder
Contact Lenze
set (on diskette) to Lenze.
Correct the parameter set.
Contact Lenze
Repeat data transfer or load Lenze
settings