Faulty behaviour of the Drive PLC
Malfunction
Communication error
Communication error
Log-in not possible
PC does not respond
No control signal on the digital
outputs (X2)
No read-in of signals on the
digital inputs (X3)
System error messages
Display
Keypad
noer
ccr
ce0
ce1
L

Troubleshooting and fault elimination

Cause
Drive PLC has no supply voltage
No connection between PC and Drive PLC
PC system-bus module 2173IB has no supply vol-
tage
(LED is OFF on the PC system-bus module)
No termination resistor (120 Ω ) in the system bus
PC system-bus module 2173IB was not initialized Follow the switch-on sequence:
Communication parameter is faulty
The system-bus module was disconnected from
the parallel port (LPT) of the PC during operation
A print job was sent to the interface/port used by
the system-bus module
Missing connection between X1/+24 and X1/O24
HIGH level of input signals is too low (<13 V)
Error
1)
PC
0
No fault
71
System error
61
Communication error to AIF
62
Communication error to
CAN-IN1 with sync control
^ÄÄK NJOQ
Cause
-
Strong interference on control ca-
bles
Ground or earth loops in the wiring
Faulty transmission of control com-
mands via AIF
CAN-IN1-object receives faulty data
or communication is interrupted
EDK10200EV3 DE/EN/FR 5.0
Remedy
Switch on supply voltage
Check system bus wiring
Instructions for PC system-bus module 2173IB
41
Plug in the supply voltage adapter for the DIN/PS2
keyboard connection
Instructions for PC system-bus module 2173IB
36
1. Plug the PC system-bus module 21731B into
LPT1 or LPTx
2. Switch on the PC
Set the communication parameter correctly
DDS "First steps", Chap. 4.4.2
Restart the PC
Restart the PC, and use the other parallel port
(LPT) for printing
Set up the connection
39
HIGH level of input signals must be between 13 V
... and 30 V
39
Remedy
-
Shield control cables
Insert the communication module
into the hand terminal
Plug-in connection - bus module
Check FIF
Check transmitter
Increase monitoring time under
C0357/1 if necessary
?