Télécharger Imprimer la page

Hitachi RCI-1,0FSR Manuel D'installation Et De Fonctionnement page 43

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 83
ELECTRICAL WIRING
6 ELECTRICAL WIRING
6.1 GENERAL INFORMATION
!
D A N G E R
Turn off the main power switch to the indoor unit and the
outdoor unit before electrical wiring work or a periodical check
is performed.
Check to ensure that the indoor fan and the outdoor fan have
stopped before electrical wiring work or a periodical check is
performed.
Protect the wires, drain pipe, electrical parts, etc. from rats
or other small animals. If not protected, rats may gnaw at
unprotected parts and at the worst, a fire will occur.
!
C A U T I O N
Install an ELB (Earth Leakage Breaker) in the power source line.
Use twisted shielded pair cable or shield pair cable for transmission
wires between the indoor and the outdoor units, and connect the
shielded part to the earth screw in the electrical box of the indoor unit
as shown below.
Wrap the field supplied insulation around the wires, and plug the
wiring connection hole with the seal material to protect the product
from any condensate water or insects.
Tightly secure the wires with the cord clamp inside the indoor unit.
Lead the wires through the knockout hole in the side cover when
using conduit.
Secure the cable of the remote control switch using the cord clamp
inside the electrical box.
6.2 ELECTRICAL WIRING CONNECTION FOR INDOOR UNIT
1 The electrical wiring connection for the indoor unit is shown
below.
Cord clamp
Wiring support plate
Electrical box
PCB
(Printed circuit
board)
Electrical box
cover
Transition wiring between indoor
unit and outdoor unit
Electrical box
Terminal board
(white) DC 5V
Terminal board (black)
1~ 230V 50Hz
Earth wiring connection screw
9
PMML0547 rev.0 - 11/2020
Piping cover
Wiring connection hole
Screw for wiring
support plate under
piping cover
Screw
(for electrical box cover)
Wiring for remote
control switch
Wiring support
plate
Cord clamp
Screw for wiring
support plate
Power source wiring
(between indoor units)

General Check
1 Make sure that the field-selected electrical components
(main power switches, circuit breakers, wires, conduit
connectors and wire terminals) have been properly selected.
Make sure that the components follow local codes and
regulations.
2 Check to ensure that the power supply voltage is within
+/-10% of the rated voltage.
3 Check the capacity of the electrical wires. If the power
source capacity is too low, the system cannot be started due
to the voltage drop.
4 Select the wire sizes according to the European Standard,
EN60 335-1. Use the wires which are not lighter than
the ordinary tough rubber sheathed flexible cord (code
designation 60245 IEC 57) or ordinary polychloroprene
sheathed flexible cord (code designation 60245 IEC 57).
5 Check to ensure that the ground wire is connected.
2 Remove the electrical box cover (1 screw).
3 Loosen two (2) screws for the wiring support plate.
4 Connect the cable of an remote control switch or an optional
extension cable to the terminals inside the electrical box
through the connecting hole in the cabinet.
5 Connect the power supply and earth wires to the terminals in
the electrical box.
6 Connect the wires between the indoor unit and the outdoor
unit to the terminals in the electrical box.
Earth terminal
Terminal board (TB1)
Terminal board (TB2)
Earth
screw
Power source cable
(1~ 230V 50Hz)
(0.75 mm
)
2
Max current: 5 A
H-Link transmission
wiring (0.75 mm
)
2
Remote control switch cable
Electrical box

Publicité

loading

Ce manuel est également adapté pour:

Rci-2,5fsrRci-3,0fsrRci-6,0fsrP-n23na2