Canceling forced settings
To cancel a forced setting, press and hold the SET key for 1 second while the forced setting is selected. The setting in progress
indicator turns off, and operation returns to forced setting selection.
13-2. Test run settings using the remote controller (Refer to Fig. 7.)
(1) Press the CHECK button on the remote controller, then press the ON/OFF operation button.
(The maximum time for a test run using the remote controller is 1 hour.)
During trial run operation "TEST" appears on the LCD display.
Temperature control is not possible in Test Run mode. Because an excessive load is placed on the equipment, do not
use this mode except when performing a test run.
(2) Perform a test run in either heating or cooling mode.
Note: The outdoor unit will not operate for approximately 3 minutes after operation is started or after operation is
stopped.
(3) If correct operation is not possible, a code appears on the remote controller LCD display.
Refer to Table 7 and correct the problem.
(4) After the test run is completed, press the CHECK button on the remote controller again. "TEST" disappears from the LCD
display.