5.16 DMC14 ELECTRONIC INSTRUMENT (AIR DRYER CONTROLLER)
set
DISPLAY
The DMC14 controller performs a double function : through the digital thermometer with an alphanumerical
display it shows the DewPoint detected by the probe in the evaporator; it controls the functioning of
condensate drain solenoid valve through the cyclic electronic timer.
The LED
indicates any alarm conditions, that may occur when:
- The DewPoint is too high;
- The DewPoint is too low;
- the probe is damaged.
If the probe is damaged the instrument displays the message "PF" (Probe Failure), and the alarm goes off
immediately. In case of alarm for a very low DewPoint (ASL fixed parameter equal to -2°C) the signal is
delayed by a fixed time (AdL parameter) of 30 sec, whereas in case of alarm for a very high the threshold value
(ASH parameter) can be set by the user and delayed by an AdH value, which can also be programmed (the
instrument has default settings that are indicated below). As soon as the DewPoint falls back into the set
temperature range the alarm is disabled.
DMC14 allows also remote annunciation of this alarm condition of the dryer :
- with dryer off or in alarm conditions there is no voltage from terminal 4 and 9 of electronic instrument
(please also see electric drawings into the attachments);
- whereas, with dryer on and correct operating DewPoint, there is voltage from terminal 4 and 9 of
electronic instrument (please also see electric drawings into the attachments).
OPERATION - When the dryer is switched on, the instrument displays the current DewPoint: display
indicates the temperature measured, expressed in Celsius (
°F) with a resolution of 1°F.
(
The condensate drain solenoid valve is activated for 2 seconds (Ton) - LED (
if standard setting.
To perform the manual test for the condensate drain, press the
SET-UP
Keep the buttons
programming. The display will show the first parameter to set (Ton); press the button
display the set value. To select the desired parameter press in sequence the button
value of the selected parameter use the buttons
following the diagram below:
Display
Ton
Activation time of the condensate drain solenoid valve.
ToF
Pause time of the condensate drain solenoid valve.
ASH
Alarm threshold for a high DewPoint.
AdH
ASH alarm time before signal.
SCL
Temperature scale.
Fixed parameters :
In any moment it is possible to exit the programming mode by pressing the buttons
same time. In case no operations are made during 30 seconds, the system exits automatically the set-up
condition.
DMC 14
°C
°F
esc
set
and
pressed simultaneously for at least 5 seconds to start the
Description
ASL (low DewPoint alarm) = -2°C
set
Button - access the set-up.
esc
Button - Exit programming / decrease value.
Button - condensate drain test / value increment.
LED
- Dryer in alarm status.
°C LED
- Display the set temperature scale (°C).
°F LED
- Display the set temperature scale (°F).
LED
- condensate drain solenoid valve on.
°C) with a resolution of 0.5°C or in Fahrenheit
esc
and
) on - each minute (ToF),
button.
set
. All the parameters can be changed
Value range
Set value
01 ... 20
01 ... 20
0.0 ... 20.0
00 ... 20
°C ... °F
AdL (signal delay) = 30 sec
esc
GB
set
again to
. To change the
Equal to
02
2 sec
01
1 min
20
20°C
20
20 min
°C
°Celsius
and
at the