Thermador PROFESSIONAL PRO GRAND PRD364JDGC Instructions D'installation page 20

Masquer les pouces Voir aussi pour PROFESSIONAL PRO GRAND PRD364JDGC:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4-Wire Connection
A unit must be connected to the power supply with a 3-
POLE, 4-CONDUCTOR cord kit rated 125/250 VOLTS, 50
AMPERES, and marked for use with ranges.
The cord kit must be attached to the range terminal block
with a strain relief (not provided) which will fit a 1"
(25.4 mm) diameter hole. If not already equipped, the cord
must also have 1/4" (6 mm) faston closed-loop lugs
attached to the free ends of the individual conductors,
preferably soldered in place.
1. Locate the terminal block on the rear of the unit and
remove cover (see Figure 17).
2. Mount strain relief (not provided with range) into the 1"
(25.4 mm) diameter hole in the back panel located
below the terminal block. Route wires up through strain
relief.
Terminal Block
Terminal Block
Terminal Block
Strain Relief
Strain Relief
3. Remove upper nuts only from the terminal block studs.
Do not remove lower nuts which secure range internal
wiring leads.
4. Secure the neutral, grounded wire of the supply circuit,
to the center stud of the terminal block with nut (see
Figure 18).
5. Secure the L1 (red) and L2 (black) power leads to the
outside terminal studs (brass colored) with nuts.
6. Remove green ground screw located beneath the
terminal block. Discard white wire.
7. Secure the bare copper ground lead to the range
chassis using the ground screw previously used for the
white wire. Be sure that neutral and ground terminals
do not touch.
8. Tighten all connections securely.
Installation Instructions
Figure 17: Strain Relief Location
Red/L1
Wire
Green/
Ground Wire
9. Reinstall the terminal block cover.
INSTALLER — show the owner the location of the circuit
breaker. Mark it for easy reference.
3-Wire Lead Connection
Where local codes and ordinances permit grounding
through neutral, and conversion of supply to 4 wire is
impractical, unit may be connected to the power supply
with a 3-POLE, 3-CONDUCTOR cord kit rated 125/250
VOLTS, 50 AMPERES, and marked for use with ranges.
The cord kit must be attached to the range back panel with
a strain relief which will fit a 1" (25.4 mm) diameter hole. If
not already equipped, the cord must also have 1/4" (6 mm)
faston closed-loop lugs attached to the free ends of the
individual conductors, preferably soldered in place.
1. Locate the terminal block on the rear of the unit and
remove cover.
2. Mount strain relief (not provided with range) into the 1"
(25.4 mm) diameter hole in the back panel located
below the terminal block (see Figure 18). Route wires
up through strain relief.
Terminal Block
Terminal Block
Terminal Block
Strain Relief
Strain Relief
Black/L2
Wire
White/
Neutral Wire
Figure 18: 4-Wire Connection
Figure 19: Strain Relief Location
English 19

Publicité

Table des Matières
loading

Table des Matières