Default Alarm Properties; Commands Menu - Icar Rpc 5Lga Notice D'utilisation

Regulateur du facteur de puissance
Masquer les pouces Voir aussi pour RPC 5LGA:
Table des Matières
Les langues disponibles

Les langues disponibles

A07
Capacitor current overload
A08
Temperature too high
A09
No-Voltage release
Voltage THD too high
A10
A11
Current THD too high
A12
Ordinary maintenance requested

14.2 Default alarm properties

A01
A02
A03
A04
A05
A06
A07
A08
A09
A10
A11
A12

15. Commands menu

The commands menu allows executing some occasional operations like reading peaks resetting, counters clearing, alarms
reset, etc.
If the Advanced level password has been entered, then the commands menu allows executing the automatic operations
useful for the device configuration.
The following table lists the functions available in the commands menu, divided by the access level required.
With controller in MAN mode, press
Press ▲ to select CMD.
Press
to access the Commands menu.
Select the desired command with
Press and hold for three seconds ▲ if you want to execute the selected command. The RPC 5LGA regulator shows OK? with
a countdown.
If you press and hold ▲ until the end of the countdown the command is executed, while if you release the key before the
end, the command is canceled.
COD
COMMAND
C01
RESET MAINTENANCE
C02
RESET STEP COUNT
C03
RESET STEP TRIMMING
C04
RESET STEP HOURS
C05
Reset max VALUES
C06
RESET WEEKLY TPF
C07
SETUP TO DEFAULT
C08
SETUP BACKUP
C09
SETUP RESTORE
The calculated capacitor current overload is higher than threshold set with
P.32 and P.33. After the alarm conditions have disappeared, the alarm
message remains shown for the following 5 min or until the user presses a
key on the front.
The panel temperature is higher than threshold set with P.39.
A no-voltage release has occurred on the line voltage inputs, lasting more
than 8ms.
The THD of the plant voltage is higher than the threshold set with P.43.
The THD of the plant current is higher than the threshold set with P.44.
The maintenance interval set with P.45 has elapsed. To reset the alarm use
the command C.01 (see Command menu).
DESCRIPTION
Undercompensation
Overcompensation
Current too low
Current too high
Voltage too low
Voltage too high
Capacitor current overload
Temperature too high
No-Voltage release
Voltage THD too high
Current THD too high
Maintenance requested
MODE
button for 5 seconds.
or
.
MODE
PSW
Usr.
Adv.
Adv.
Adv.
Adv.
Usr.
Adv.
Adv.
Usr.
DESCRIPTION
Reset maintenance service interval.
Reset step operation counters.
Reload originally programmed power into step trimming.
Reset step operation hour meters.
Reset maximum peak values.
Resets weekly total power factor history.
Resets setup programming to factory default.
Makes a backup copy of user setup parameters settings.
Reloads setup parameters with the backup of factory settings.
15 min
120 s
30 s
60 s
60 s
15 min
3 min
60 s
0 s
60 s
60 s
0s
p. 33 / 60