• Simply hold the dongle up to the front panel, connecting the plugs to the relevant connectors, and the device will be
acknowledged as shown by the LINK LED on the programming dongle flashing green.
USB programming dongle code A25060046580008
10. Parameter setting with PC
• You can use the PFC Remote monitoring software to transfer (previously programmed) set-up parameters from the RPC
5LGA regulator to the hard drive of the PC and vice versa.
The parameter may be partially transferred from the PC to the RPC 5LGA regulator, transferring only the parameters of the
•
specified menus.
11. Parameter setting (setup) from front panel
To access the programming menu (setup) :
To enter parameter programming the unit must be in TEST mode (first programming)
•
or in MAN mode.
From the normal measurement display, press and hold
•
the main display.
If you have set the password (P.21 = ON) instead of SET the display shows PAS (password entry request). Set the numeric
•
password using ▲ ▼ and then press
If the password is correct the unit will show OK U or OK A depending on the entered password is user or the advanced level.
•
The password can be defined with parameters P.22 and P.23. Factory default is 001 and 002 respectively.
If the entered password is wrong the unit will show ERR.
•
After having entered the password, the access is enabled until the unit is re-initialized or for 2 minutes without pressing any
•
key.
After having entered the password, repeat the procedure to access the parameter setting.
•
Indication of
TEST mode
Firmware
revision
MAN
mode
Tot kvar
inserited
MODE
to move to next digit.
WIFI programming dongle code A25060046580009
Total
number
of steps
Model
variant
Connected
steps
Manual step
selection
enabled
for 3 seconds to recall the main menu. SET is displayed on
p. 25 / 60