Man And Aut Mode; Man Mode (Man); Aut Mode (Aut); Measures - Icar Rpc 5Lga Notice D'utilisation

Regulateur du facteur de puissance
Masquer les pouces Voir aussi pour RPC 5LGA:
Table des Matières
Les langues disponibles

Les langues disponibles

5.1. MAN and AUT Modes
• The icons AUT and MAN indicate the operating mode automatic or manual.
• To change the mode, press and hold the
• The operating mode remains stored even after removing and reapplying the power supply voltage.
5.2. MAN Mode
• When the unit is in manual mode, you can select one of the steps and manually connected or disconnect it.
• In addition to the specific icon, the alphanumeric display shows MAN in order to highlight the manual mode condition.
Press
to view the other measurements as usual.
MODE
• While the display shows MAN, it is possible to select the step to be switched on or off. To select a step, use the ▲or
▼buttons. The selected step will flash quickly.
• Press
to activate or deactivate the selected step.
MODE
• If the selected step has not yet exhausted the reconnection time, the
been accepted and will be conducted as soon as possible.
Manual configuration of the steps is maintained even when the power supply voltage is removed. When the power returns,
the original state of the steps is restored.
5.3. AUT Mode
• In automatic mode, the controller calculates the optimum configuration of capacitor steps in order to reach the set cosϕ.
• The selection criteria takes into account many variables such as: the power of each step, the number of operations, the total
time of use, the reconnection time, etc.
• The controller displays the imminent connection or disconnection of the steps with the flashing of their identification number
(left). The flashing can last in cases in which the insertion of a step is not possible due to the reconnection time (discharge
time of the capacitor).
• The device initiates automatic corrections when there is an average reactive power request (delta-kvar) higher than 50% of
the smallest step, and the measured cosϕ is different from the setpoint.

6. Measures

• The RPC 5LGA controller provides a set of measurements displayed on the alphanumeric display, in conjunction with the
current cosϕ that is always displayed on the main display.
• Press the
key to scroll through the measures in rotation.
MODE
• After 30 seconds without pressing any buttons, the display automatically returns to the default measurement defined by P.47.
• If P.47 is set on the ROT, then the measures rotate automatically every 5 seconds.
• At the bottom of the list of measures it is possible to set the setpoint of the cosϕ, acting on the same value set with P.19.
Below is a table with the measurements displayed.
Measure
Icon
Delta-kvar
∆kvar Kvars needed to reach the cosphi setpoint. If delta-kvar is positive cpacitors need to be inserted, if
kvar
∆STEP
button for 1 sec.
MAN
mode
Tot kvar
inserited in
MAN
Description
negative to be disconnected.
Total kvar of the plant.
Number of equal steps to achieve the target power factor.
icon will flash to indicate that the transaction has
MODE
Select step
Change step status
MODE
Connected
steps
Manual
step
selection
p. 22 / 60