ALARM MENU
COD
DESCRIPTION
P.61
A01 Alarm enable
P.62
A01 alarm delay
P.63
A01 delay uom
...
....
P.94
A12 Alarm enable
P.95
A12 alarm delay
P.96
A12 delay uom
P.61 - Enable alarm A01 and defines the behavior of the controller when the alarm is active:
OFF - Alarm disabled
ON - Alarm enabled, only visual
ALA - Alarm enabled, global alarm relay energized (if set)
DISC - Alarm enabled, logoff step
A + D = Alarm relay energized and disconnection of the steps.
Note: When you access the parameters P61, P.64, P67, etc., the auxiliary display shows the relative alarm code.
P.62 - Delay alarm A01.
P.63 - Unit of delay alarm A01.
P.64 – Like P.61 for alarm A02.
P.65 – Like P.62 for alarm A02.
P.66 – Like P.63 for alarm A02.
...
P.94 – Like P.61 for alarm A12.
P.95 – Like P.62 for alarm A12.
P.96 – Like P.63 for alarm A12.

14. Alarms

• When an alarm is generated, the display will show an alarm icon, the code and the description of the alarm in the language
selected.
• If the navigation keys in the pages are pressed, the scrolling message showing the alarm indications will disappear
momentarily, to reappear again after 30 seconds.
• Alarms are automatically resetted as soon as the alarm conditions that have generated them disappear.
• In the case of one or more alarms, the behaviour of the RPC 5LGA regulator depends on the properties settings of the active
alarms.

14.1 Alarm description

COD
ALLARME
A01
Undercompensation
A02
Overcompensation
A03
Current too low
A04
Current too high
A05
Voltage too low
A06
Voltage too high
PSW
UoM
DEF
Adv
ALA
Adv
15
Adv
min
...
...
...
Adv
ALA
Adv
120
Adv
sec
DESCRIPTION
In automatic mode, all the available steps are connected but the cosphi is
still more inductive than the setpoint.
In automatic mode, all the steps are disconnected but the cosphi is still more
capacitive than the setpoint.
The current flowing in the current inputs is lower than minimum measuring
range.
This condition can occour normally if the plant has no load.
The current flowing in the current inputs is lower than minimum measuring
range.
The measured voltage is lower than the threshold set with P.42.
The measured voltage is higher than the threshold set with P.41.
RANGE
OFF
ON
ALA
DISC
A+D
0-240
Min
Sec
...
OFF
ON
ALA
DISC
A+D
0-240
Min
Sec