Carry out all control and handling without voltage.
As a minimum security measure in this operation, you should always follow the so-called 5 golden
rules:
1.
Disconnect.
2.
Prevent any possible feedback.
3.
Check there is no voltage.
4.
Ground and short circuit.
5.
Protect from live elements, if any, and put up safety signs around the work zone.
Until these five steps are completed, the work area cannot be considered voltage-free and any work
performed will be considered to be work on live equipment.
Potential hazards for people
Bear in mind the following warnings concerning personal safety.
DANGER: Crushing and joint injuries.
Always follow the indications in the manual on moving and placing the unit.
The weight of this unit can cause injury if not handled correctly.
Potential hazards for the equipment
Bear in mind the following warnings concerning protection of the equipment.
The unit requires impurity-free air flow while it is operating.
Keeping the unit in the upright position and the inlets free of obstacles is essential for this air flow to
reach the inside.
After all duly authorised handling, check that the equipment is ready to start operation. Only after
this can you connect it following the instructions in the manual.
Do not touch boards or electronic components. The more sensitive components can be damaged or
destroyed by static electricity.
Do not disconnect or connect any of the terminals while the unit is operating. Disconnect and check
for absence of voltage first.

3.2. Personal Protective Equipment (PPE)

When working on the unit, use the following safety equipment recommended by Ingeteam as a minimum.
Name
Safety footwear
Helmet
Helmet with face shield
Working clothes
Dielectric gloves
Tools and / or equipment used in live work must have at least Category III-1000 Volts insulation.
Should the country's regulations demand another kind of personal protection, the equipment recommended by
Ingeteam should be appropriately supplemented.
14
In compliance with standard UNE-EN-ISO 20345:2012
In compliance with standard EN 397:1995
In compliance with Standard UNE-EN 166:2002, wherever there are directly
accessible live parts.
Close-fitting, non-flammable, 100% cotton
In compliance with standard EN 60903:2005
ABA2020IQM01_A - Installation and Operation Manual