ELECTRICAL AND CONTROL SETTINGS

DSW1: Additional setting 0
Factory setting. No setting is required.
Factory setting
?
N O T E
In case of installing the "Cooling kit" accessory, set the pin 4 of DSW1 to
ON in order to enable the cooling operation.

DSW2: Unit capacity setting
No setting is required.
2.0 HP
4.0 HP

DSW3: Additional setting 1
Setting before shipment
1-step heater for 3-phase unit

DSW4: Additional setting 2
Setting before shipment
DHW defrost
Heater forced OFF
Unit and installation pipes antifreeze
protection
Standard / ECO water pump operation
Electric heater or boiler emergency mode
DHW tank's heater operation
DHW 3-way valve forced ON
20
PMML0338B rev.1 - 03/2016
2.5 HP
3.0 HP
5.0 HP
6.0 HP
!
C A U T I O N
Never turn all DSW4 dip switch pins ON. If this happens, the software
of the unit will be removed.
Never activate "Heater Forced OFF" and "Electric heater or boiler
emergency mode" at the same time.

DSW5: Additional setting 3
In the cases where the outdoor unit is installed into a location
where its own outdoor ambient temperature sensor can not
give a suitable temperature measurement to the system, it
is available the 2nd outdoor ambient temperature sensor as
accessory. By means of DSW1&2 setting, the preferable sensor
for each circuit can be selected.
Factory setting
Outdoor unit sensor for circuits 1 and 2.
Outdoor unit sensor for circuit 1; Auxiliary
sensor for circuit 2.
Auxiliary sensor for circuit 1; Outdoor unit
sensor for circuit 2.
Auxiliary sensor instead of outdoor unit
sensor for both circuits.
4-20 mA setting temperature
(Only manual operation)
Use the maximum temperature value
between Two3 (boiler / heater thermistor)
and Two (water outlet thermistor) for water
control

DSW6: Not used
7
8
Factory setting
(Do not change)
7
8

DSW7: Additional setting 4
7
8
Factory setting
7
8
Defrost for the water electric heater
7
8

DSW8: Not used
Factory setting
7
8
(Do not change)

7
8
DSW18: Not used
Factory setting
7
8
(Do not change)