Hitachi YUTAKI S COMBI Serie Manuel D'utilisation page 26

Masquer les pouces Voir aussi pour YUTAKI S COMBI Serie:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 113
ELECTRICAL AND CONTROL SETTINGS
5.4 WIRING SIZE AND MINIMUM REQUIREMENTS OF THE PROTECTION DEVICES
!
C A U T I O N
Check to ensure that the field supplied electrical components (mains power switches, circuit breakers, wires, connectors and wire terminals) have
been properly selected according to the electrical data indicated on this chapter and they comply with national and local codes. If it is necessary,
contact with your local authority in regards to standards, rules, regulations, etc.
Use a dedicated power circuit for the indoor unit. Do not use a power circuit shared with the outdoor unit or any other appliance.
Use wires which are not lighter than the polychloroprene sheathed flexible cord (code designation 60245 IEC 57).
Power
Model
supply
RWD-(2.0-3.0)
1~ 230V
NW(S)E-(200/260)S(-K)
50Hz
1~ 230V
50Hz
RWD-(4.0-6.0)
NW(S)E-(200/260)S(-K)
3N~
400V
50Hz
!
C A U T I O N
Ensure specifically that there is an Earth Leakage Breaker (ELB)
installed for the units (outdoor and indoor unit).
If the installation is already equipped with an Earth Leakage Breaker
(ELB), ensure that its rated current is large enough to hold the current
of the units (outdoor and indoor unit).
16
PMML0338B rev.1 - 03/2016
Operation mode
Without electric heaters
With electric heater
With DHW tank heater
With electric and DHW tank heaters
Without electric heaters
With electric heater
With DHW tank heater
With electric and DHW tank heaters
Without electric heaters
With electric heater
With DHW tank heater
With electric and DHW tank heaters
Power supply
Max.
cables
current
(A)
EN60335-1
0.2
2 x 0.75 mm² + GND
15
2 x 2.5 mm² + GND
13
2 x 2.5 mm² + GND
27
2 x 6.0 mm² + GND
0.3
2 x 0.75 mm² + GND
29
2 x 6.0 mm² + GND
13
2 x 2.5 mm² + GND
42
2 x 10.0 mm² + GND
0.3
4 x 0.75 mm² + GND
10
4 x 2.5 mm² + GND
13
4 x 2.5 mm² + GND
22
4 x 6.0 mm² + GND
?
N O T E
Electric fuses can be used instead of magnetic Circuit Breakers (CB).
In that case, select fuses with similar rated values as the CB.
The Earth Leakage Breaker (ELB) mentioned on this manual is also
commonly known as Residual Current Device (RCD) or Residual
Current Circuit Breaker (RCCB).
The Circuit Breakers (CB) are also known as Thermal-Magnetic
Circuit Breakers or just Magnetic Circuit Breakers (MCB).
Transmitting
ELB
CB
cables
(no. of poles/A/
(A)
mA)
EN60335-1
5
16
2/40/30
16
32
5
32
2/40/30
2 x 0.75 mm
2
16
50
2/63/30
5
15
4/40/30
15
25

Hide quick links:

Publicité

Table des Matières
loading

Table des Matières