Carrier Aquasmart TOUCH Pilot Instructions De Fonctionnement Et D'entretien page 81

Table des Matières

Publicité

Code
Description
Running Failures (suite)
P-37
Circuit A - Repeated high discharge gas overrides
Circ A – High condensing temperature out of map compressor
P-38
Circuit B – Repeated high discharge gas overrides
Circ B – High condensing temperature out of map compressor
P-39
Circuit C – Repeated high discharge gas overrides
Circ C – High condensing temperature out of map compressor
P-40
Circuit A – Repeated low suction temp overrides
Circuit A – Repeated low suction temp overrides
P-41
Circuit B – Repeated low suction temp overrides
Circuit B – Repeated low suction temp overrides
P-42
Circuit C – Repeated low suction temp overrides
Circuit C – Repeated low suction temp overrides
P-43
Low entering water temperature in heating
P-50
Refrigerant Leakage Detection
P61-x
Condenser Water loop process Failure
P62-x
Water loop process Failure
P-63
Circuit A High pressure switch Failure
P-64
Circuit B High pressure switch Failure
P-67
Circuit A Low Oil Pressure
P-68
Circuit B Low Oil Pressure
P-69
Circuit C Low Oil Pressure
P-70
Circuit A Max Oil Filter Differential Pressure
P-71
Circuit B Max Oil Filter Differential Pressure
P-72
Circuit C Max Oil Filter Differential Pressure
P-73
Condenser pump #1 fault
P-74
Condenser pump #2 fault
P-75
Circuit A Low Oil Level
P-76
Circuit BLow Oil Level
P-77
Circuit C Low Oil Level
P-78
Circuit A High Discharge Temperature
P-79
Circuit B High Discharge Temperature
P-80
Circuit C High Discharge Temperature
P-81
Circuit A Low Economizer Pressure or Suction Valve Closed
P-82
Circuit B Low Economizer Pressure or Suction Valve Closed
P-83
Circuit C Low Economizer Pressure or Suction Valve Closed
P-84
Circuit A High Oil Filter Drop Pressure
P-85
Circuit B High Oil Filter Drop Pressure
P-86
Circuit C High Oil Filter Drop Pressure
P-87
Circuit A Slide Valve Control Unverifiable
P-88
Circuit B Slide Valve Control Unverifiable
P-89
Circuit C Slide Valve Control Unverifiable
P-90
Cooler flow switch setpoint configuration failure
P-91
Circuit A Free Cooling Valve Incoherent Position
Cooler flow switch failure
P-92
Circuit B Free Cooling Valve Incoherent Position
P-93
Circuit C Free Cooling Valve Incoherent Position
P-94
Circuit A Free Cooling Operation Failure
P-95
Circuit B Free Cooling Operation Failure
P-96
Circuit C Free Cooling Operation Failure
P-97
Water Heat Exchanger Temperature Sensors Swapped
Cooler Water Heat Exchanger Temperature Sensors Swapped
P-98
Condenser Water Heat Exchanger Temperature Sensors Swapped
P-99
Refrigerant Leakage Detection
P-100
Incorrect Indoor Fan Status
P-201
Low Supply Air Temperature Alarm
P-202
Heat Exchanger Failure
P-203
Extract Fan failure
P-204
Supply Fan failure
P-205
Electrical pre-heater maximum temp alarm
P-206
Electrical heater, maximum temp alarm
P-207
Frost protection of pre heat hot water coil
P-208
Frost protection of booster hot water coil
P-209
External Fire
Formule de calcul appliqué
Le code des alarmes P-nn est calculé de la façon sui-
vante:
Code = 10000 + nn
Exemple pour une alarme P-12: nn= 12
Code Alarme NSM correspondant à P-12= 10012
Le code des alarmes P6y-x est calculé de la façon
suivante:
Code= 11000 + y * 100 + x
Exemple pour une alarme P61-1: y = 1 et x = 1
Code Alarme NSM correspondant à P61-1 = 11101
Le code des alarmes P-nn est calculé de la façon sui-
vante:
Code= 10000 + nn
Exemple pour une alarme P-201: nn = 201
Code Alarme NSM correspondant à P-201= 10201
81