Code d'alarme
Code
Description
Compressor failures
Ax-01
Compressor Ax Motor Temperature Too High
Comp. Ax failed: Motor protection Kriwan Safety Open
Ax-02
Compressor Ax Crankase Heater Failure
Compressor A Motor temperature out of range
Ax-03
Compressor Ax High Pressure Switch
Ax-04
Compressor Ax Motor Temperature Sensor PTC Out Of Range
Compressor A Over current
Ax-05
Compressor Ax Power Reset
Compressor A Locked rotor
Ax-06
Compressor Ax Low Control Voltage Alert
Compressor A Phase loss L1
Ax-07
Compressor Ax Phase loss L2
Ax-08
Compressor Ax Phase loss L3
Ax-09
Compressor Ax Low current alarm
Ax-10
Compressor Ax Y delta starter current increase failure alarm
Ax-11
Compressor Ax Contactor failure
Ax-12
Compressor Ax Unable to stop motor
Ax-13
Compressor Ax Phase reversal
Ax-14
Compressor Ax MTA configuration fault
Ax-15
Compressor Ax Configuration switch mismatch
Ax-16
Compressor Ax Unexpected switch setting change
Ax-17
Compressor Ax Power on reset
Ax-18
Compressor Ax UL 1998 critical section software error
Ax-19
Compressor Ax UL 1998 current measure dual channel mismatch
Bx-01
Compressor Bx Motor Temperature Too High
Bx-02
Compressor Bx Crankase Heater Failure
Compressor Bx Motor temperature out of range
Bx-03
Compressor Bx High Pressure Switch
Bx-04
Compressor Bx Motor Temperature Sensor PTC Out Of Range
Compressor Bx Over current
Bx-05
Compressor Bx Power Reset
Compressor Bx Locked rotor
Bx-06
Compressor Bx Low Control Voltage Alert
Compressor Bx Phase loss L1
Bx-07
Compressor Bx Phase loss L2
Bx-08
Compressor Bx Phase loss L3
Bx-09
Compressor Bx Low current alarm
Bx-10
Compressor Bx Y delta starter current increase failure alarm
Bx-11
Compressor Bx Contactor failure
Bx-12
Compressor Bx Unable to stop motor
Bx-13
Compressor Bx Phase reversal
Bx-14
Compressor Bx MTA configuration fault
Bx-15
Compressor Bx Configuration switch mismatch
Bx-16
Compressor Bx Unexpected switch setting change
Bx-17
Compressor Bx Power on reset
Bx-18
Compressor Bx UL 1998 critical section software error
Bx-19
Compressor Bx UL 1998 current measure dual channel mismatch
Cx-01
Compressor Cx Motor Temperature Too High
Cx-02
Compressor Cx Crankase Heater Failure
Compressor Cx Motor temperature out of range
Cx-03
Compressor Cx High Pressure Switch
Cx-04
Compressor Cx Motor Temperature Sensor PTC Out Of Range
Compressor Cx Over current
Cx-05
Compressor Cx Power Reset Compressor Cx Locked rotor
Cx-06
Compressor Cx Low Control Voltage Alert
Compressor Cx Phase loss L1
Cx-07
Compressor Cx Phase loss L2
Cx-08
Compressor Cx Phase loss L3
Cx-09
Compressor Cx Low current alarm
Cx-10
Compressor Cx Y delta starter current increase failure alarm
Cx-11
Compressor Cx Contactor failure
Cx-12
Compressor Cx Unable to stop motor
Cx-13
Compressor Cx Phase reversal
Cx-14
Compressor Cx MTA configuration fault
Cx-15
Compressor Cx Configuration switch mismatch
Cx-16
Compressor Cx Unexpected switch setting change
Cx-17
Compressor Cx Power on reset
Cx-18
Compressor Cx UL 1998 critical section software error
Cx-19
Compressor Cx UL 1998 current measure dual channel mismatch
Formule de calcul appliqué
Le code des alarmes Ax-nn est calculé de la façon sui-
vante:
Code= 1000 + 100 * x + nn
Exemple pour une alarme A1-03: x= 1 et nn= 3
Code Alarme NSM correspondant à A1-03= 1103
Le code des alarmes Bx-nn est calculé de la façon sui-
vante:
Code= 2000 + 100 * x + nn
Exemple pour une alarme B2-13: x= 2 et nn= 13
Code Alarme NSM correspondant à B2-13= 2213
Le code des alarmes Cx-nn est calculé de la façon sui-
vante:
Code= 3000 + 100 * x + nn
Exemple pour une alarme C4-09: x= 4 et nn= 9
Code Alarme NSM correspondant à C4-09= 3409