Code
Description
Communication Failures
Co-Ax
Loss of communication with Compressor Board Ax
Co-Bx
Loss of communication with Compressor Board Bx
Co-Cx
Loss of communication with Compressor Board Cx
Co-Ex
Loss of communication with EXV Board Number x
Co-Fx
Loss of communication with Fan Board Number x
Co-O1
Loss of communication with Auxiliary Board Number 1
Loss of communication with Free Cooling Board 1
Co-O2
Loss of communication with Auxiliary Board Number 2
Loss of communication with Free Cooling Board 2
Loss of communication with Electric heater board
Co-O3
Loss of communication with Energy Management Board
Co-O4
Loss of communication with Heat Reclaim Board
Loss of communication with Heat Reclaim Board
Co-O5
Loss of communication with Free Cooling Board Circuit A
Co-O6
Loss of communication with Free Cooling Board Circuit B
Co-O7
Loss of communication with Free Cooling Board Circuit C
Co-Vx
Loss of communication with Drive X
CoDr1
Loss of communication with Drive 1
CoDr2
Loss of communication with Drive 2
CoDr3
Loss of communication with Drive 3
Ct-01
Circuit A Welded Contactor Failure
Ct-02
Circuit B Welded Contactor Failure
Ct-03
Circuit C Welded Contactor Failure
FC-01
Illegal factory configuration Number #1 to nn
FC-nO
No factory configuration
MC-01
Master chiller configuration error Number #1 to nn
Running Failures
P-01
Water Heat Exchanger Freeze Protection
P-02
Circuit A Condenser Freeze Protection
P-03
Circuit B Condenser Freeze Protection
P-04
Circuit C Condenser Freeze Protection
P-05
Circuit A Low Suction Temperature
P-06
Circuit B Low Suction Temperature
P-07
Circuit C Low Suction Temperature
P-08
Circuit A High Superheat
P-09
Circuit B High Superheat
P-10
Circuit C HighSuperheat
P-11
Circuit A Low Superheat
P-12
Circuit B Low Superheat
P-13
Circuit C Low Superheat
P-14
Cooler Interlock Failure
P-15
Condenser Flow Switch Failure
P-16
Compressor A1 Not Started or Pressure Increase not established
P-17
Compressor A2 Not Started or Pressure Increase not established
P-18
Compressor A3 Not Started or Pressure Increase not established
P-19
Compressor A4 Not Started or Pressure Increase not established
P-20
Compressor B1 Not Started or Pressure Increase not established
P-21
Compressor B2 Not Started or Pressure Increase not established
P-22
Compressor B3 Not Started or Pressure Increase not established
P-23
Compressor B4 Not Started or Pressure Increase not established
P-24
Compressor C1 Not Started or Pressure Increase not established
P-25
Compressor C2 Not Started or Pressure Increase not established
P-26
Compressor C3 Not Started or Pressure Increase not established
P-27
Compressor C4 Not Started or Pressure Increase not established
P-28
Electrical Box Thermostat or Power Reverse Phase Detection
Customer Interlock Failure
P-29
Loss of communication with NSM
P-30
Master/Slave communication Failure
P-31
Unit is in CCN emergency stop
P-32
Water pump #1 default
P-33
Water pump #2 default
P-34
Circuit A Reclaim Operation Failure
P-35
Circuit A Reclaim Operation Failure
80
Formule de calcul appliqué
Le code des alarmes Co-Yx est calculé de la façon sui-
vante:
Code= 4000 + x ou dernier chiffre
Si -A ajouter 100
Si -B ajouter 200
Si -C ajouter 300
Si -E ajouter 400
Si -F ajouter 500
Si -O ajouter 600
Si -V ajouter 700
Si Dr ajouter 800
Exemple pour une alarme Co-O2: x= 2 et -O
Code Alarme NSM correspondant à Co-O2= 4602
Exemple pour une alarme Co-V1: x= 1 et -V
Code Alarme NSM correspondant à Co-V1= 4701
Le code des alarmes Co-Yx est calculé de la façon sui-
vante:
Code= 6000 + nn
Exemple pour une alarme Ct-02: nn= 2
Code Alarme NSM correspondant à Ct-02= 6002
Le code des alarmes FC-nn est calculé de la façon sui-
vante:
Code= 7000 + nn
Exemple pour une alarme FC-01: nn = 1
Code Alarme NSM correspondant à FC-01= 7001
Le code de l'alarme FC-nO est 8000
Le code des alarmes MC-nn est calculé de la façon sui-
vante:
Code= 9000 + nn
Exemple pour une alarme MC-01: nn= 1
Code Alarme NSM correspondant à MC-01= 9001
Le code des alarmes P-nn est calculé de la façon suivante:
Code = 10000 + nn
Exemple pour une alarme P-12: nn= 12
Code Alarme NSM correspondant à P-12= 10012