Wiring And Grounding; Operation; Rotation; Maintenance - Xylem GOULDS Prime Line SP Manuel D'instructions

Masquer les pouces Voir aussi pour GOULDS Prime Line SP:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

PIPING – DISCHARGE
• Install a tee at the discharge connection of the pump. The
top opening of the tee is required for initial priming. See
Figure 1.

WIRING AND GROUNDING

Install, ground and wire accord-
WARNING
ing to local and National Electri-
cal Code requirements.
Install an all leg electrical power
disconnect switch near the
pump.
Disconnect electrical power, be-
Hazardous voltage
can shock, burn or
fore installing or servicing pump.
cause death.
Electrical supply MUST match pump's nameplate
specifications. Incorrect voltage can cause fire,
damage to the motor, and voids warranty.
Motors without built-in protection MUST be pro-
vided with contactors and thermal overloads for
single phase motors, or starters with heaters for
three phase motors. See motor nameplate.
• Follow motor manufacturer's wiring diagram on the mo-
tor nameplate or terminal cover carefully.
• Use only copper wire to motor and ground. The ground
wire MUST be at least as large as the wire to the motor.
Wires should be color coded for ease of maintenance.
FAILURE TO PERMANENTLY GROUND
WARNING
THE PUMP, MOTOR AND CONTROLS
Hazardous
BEFORE CONNECTING TO ELECTRI-
voltage
CAL POWER CAN CAUSE SHOCK,
BURNS, OR DEATH.

OPERATION

SPLASHING OR IMMERSING OPEN
WARNING
DRIP PROOF MOTORS IN WATER
CAN CAUSE FIRE, SHOCK, BURNS OR
DEATH.
Hazardous voltage
can shock, burn or
cause death.
OPERATION WITHOUT PRIME, OR
WARNING
AGAINST A CLOSED DISCHARGE
VALVE, CAN GENERATE HOT WATER
OR STEAM CAUSING INJURY OR
PROPERTY DAMAGE OR EXPLOSION
RESULTING IN SERIOUS PERSONAL IN-
JURY, PROPERTY DAMAGE OR DEATH.
Extreme heat can
cause personal injury
or property damage.
4
• Fill pump through opening in top of tee with clean water.
See Figure 1.
• Install pipe plug in top using Teflon™ tape or equivalent
on male threads.
NOTICE: IF PUMP IS DRAINED OR SHUT OFF DURING
PRIMING PERIOD, ENSURE CASING IS
REFILLED BEFORE RESTARTING PUMP.
• Start the pump motor and wait for system pressure to sta-
bilize. If system pressure is surging, or prolonged pressure
drop is experienced, the system may not be completely
primed.

ROTATION

NOTICE: INCORRECT ROTATION MAY CAUSE
DAMAGE TO THE PUMP AND VOIDS THE
WARRANTY.
• Correct rotation is right hand, CLOCKWISE when viewed
from the motor end.
• Single phase motors with more than 4 wires (leads) may
be reversible designs. Insure that the motor is rotating
in the correct direction. See motor nameplate for wiring
instructions.
• Three phase unit rotation may be checked by removing
motor end cap or plug and observing rotation of motor
shaft. To reverse rotation, reverse any two of the three
motor leads.

MAINTENANCE

FAILURE TO DISCONNECT AND LOCK-
WARNING
OUT ELECTRICAL POWER BEFORE AT-
TEMPTING ANY MAINTENANCE CAN
CAUSE SEVERE PERSONAL INJURY.
Hazardous Machinery
WARNING
FAILURE TO RELIEVE SYSTEM PRES-
SURE AND DRAIN SYSTEM BEFORE
ATTEMPTING ANY MAINTENANCE
CAN CAUSE SERIOUS PERSONAL
INJURY OR PROPERTY DAMAGE.
Hazardous pressure can
cause personal injury or
property damage.
• No lubrication is required on pump. For motor lubrica-
tion, refer to and follow manufacturer's instructions.
Seasonal Service
• To REMOVE pump from service, remove all drain plugs
and drain all piping.
• To RETURN pump to service, replace all drain plugs us-
ing Teflon™ tape or equivalent.
• Reconnect suction line if removed, examine union and
repair if necessary.
• Reprime and operate pump following all instructions and
warnings in the "OPERATION" section of manual.