Access To Terminal Blocks Eats30N - Eats30H; Hardwired Input/Output Connection (Eu) Eats30N - Eats30H; Input/Output Connection (Us) Eats30P - Eaton ATS 30 Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
4. Power cables connection
4.2

Access to terminal blocks EATS30N - EATS30H

4.3

Hardwired Input/Output connection (EU) EATS30N - EATS30H

To UPS 1
Cable cross sections
Terminal
Wire
position
function
L1 / L2
Phase
N1 / N2
Neutral
Ground
4.4

Input/Output connection (US) EATS30P

Page 8
To UPS 2
To load
Terminal wire
size rating
32A
1. Connect input power cables to two
UPSs (UPS1 (S1) is the preferred
source).
2. Connect output power cable to
load.
Minimum input
Tightening
wire size
torque
10 AWG
14Kgf-cm
To load
To UPS 2
To UPS 1
ATS-01_EN

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Eats30nEats30hEats30p

Table des Matières