Specifications - Eaton ATS 30 Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14

7. Specifications

Table 1. Model list
Model
EATS30N
EATS30H
EATS30P
Table 2. Weights and dimensions
Model
EATS30N
EATS30H
EATS30P
Table 3. Electrical input connections
Model
EATS30N - EATS30H
EATS30P
Table 4. Electrical output connections
Model
EATS30N - EATS30H
EATS30P
Table 5. Environmental and safety
Safety
EMI
EMS
Operating temperature
Storage temperature
Relative humidity
Operating altitude
Audible noise
Page 12
Operating voltage
Current rating
180V to 264V
30A for CE
24A for UL
24A for UL
Dimensions H x W x D (inch/mm)
1.7 x 17.4 x 15.4 / 43 x 440 x 390
1.7 x 17.4 x 15.4 / 43 x 440 x 390
1.7 x 17.4 x 15.4 / 43 x 440 x 390
Input connection
Hardwired
L6-30P
Output connection
Hardwired
L6-30R
UL (US) (UL 60950) (EATS30H - EATS30P)
CE (EU) (IEC 60950)
PSE (JP)
CISPR22 Class A and FCC Class A
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
0 to 35°C (32°F to 95°F) @30A input (EATS30N only)
0 to 40°C (32°F to 104°F) @25.6A input
-15 to 50°C / 5 to 122°F
5 to 95% RH (no condensing)
0 to 2000 meters (0 to 6252 ft)
< 45 dBA measured at a distance of 1 meter in front of the ATS under
full-load condition
Operating frequency
45Hz to 65Hz
Weight (lb/kg)
10.6 / 4.8
10.6 / 4.8
17 / 7 .7
ATS-01_EN

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Eats30nEats30hEats30p

Table des Matières