8. SNMP IPv6 for ATS
8.6
ATS Command Settings
Command
Description
Log
Report the event code and time of prior
transfers.
Tprev[1..9]
Report the time of prior transfer/event.
Tprev1 is the most recent time.
Event[1..9]
Report the event code for prior transfer.
Event1 is the most recent event.
ClearLog
Clear event log.
SetTime
Set the present time.
SetDate
Set the present date.
SetPrefer
Set the preferred source.
SetDevID
Set the unit device ID.
SetVtp2s
Set the primary to secondary trip voltage.
SetVts2p
Set the secondary to primary trip voltage.
SetVbp2s
Set the primary to secondary brownout
voltage.
SetVbs2p
Set the secondary to primary brownout
voltage.
SetTdp2s
Set the recover time of transfer from primary
to secondary.
SetTds2p
Set the recover time of transfer from
secondary to primary.
SetMvs1
Set the max voltage of comparing cycles for
primary AC blackout.
SetMvs2
Set the max voltage of comparing cycles for
secondary AC blackout.
SetMts1
Set the max time of comparing cycles for
primary AC blackout.
SetMts2
Set the max time of comparing cycles for
secondary AC blackout.
Page 6
Parameter
Response
1 ~ 10
hh:mm:ss MM/DD/YYYY
hh:mm:ss MM/DD/YYYY
hh:mm:ss
[MM/DD/YYYY]
MM/DD/YYYY
1 or 2
<20 characters>
alphanumeric
only
165.0 ~ 175.0
165.0 ~ 175.0
180.0 ~ 264.0
180.0 ~ 264.0
12.0 ~ 1800.0
12.0 ~ 1800.0
30 ~ 50
30 ~ 50
2.0 ~ 4.0
2.0 ~ 4.0
0x#
0x#