6.1 Technical specifications

Evolution
Output power
AC input power
Rated input voltage
Input-voltage range
50 Hz input-frequency range
60 Hz input-frequency range
Output on battery power
Voltage
Frequency
Battery (sealed lead acid,
maintenance free)
Tower model
Rack model
Environment
Operating temperature range
Storage temperature range
Humidity
Noise level
(1) The high and low thresholds can be adjusted using Personal Solution-Pac software.
(2) Up to 40 Hz in extended frequency mode (programmable using Personal Solution-Pac software).
(3) Adjustable to 200 V (10% derating of output power) / 208 V / 220 V / 230 V / 240 V.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16A, 250V which is
IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20A, 250V.
This product is designed for IT power distribution system.
Filter
Transformer
”AVR”
Charger
650 / 650 Rack
850 / 850 Rack
650 VA /
850 VA /
420 W
600 W
Single phase 220~240 V
230 V (+6% / -10%)
1 x 12 V - 9 Ah
2 x 12 V - 7.2 Ah
2 x 6 V - 9 Ah
4 x 6 V - 7.2 Ah
0 to 35°C
20 to 90% (without condensation)

6. Appendices

Inverter
Battery
1150 / 1150 Rack
1150 VA /
770 W
(1)
160 V to 294 V
(2)
47 Hz to 70 Hz
(2)
56.5 Hz to 70 Hz
(3)
50/60 Hz ±0.1 Hz
2 x 12 V - 9 Ah
4 x 6 V - 9 Ah
-25°C to 40°C
< 40 dbA
1550 / 1550 Rack
1550 VA /
1100 W
3 x 12 V - 9 Ah
6 x 6 V - 9 Ah
0 to 40°C
34008235EN/AC - Page 19