Appendices; Technical Specifications - Eaton Evolution S 1250 RT 2U Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour Evolution S 1250 RT 2U:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6.1

Technical Specifications

Output power
AC input power
w Rated input voltage
w Input-voltage range
w Input-frequency range
Output on battery power
w Voltage
w Frequency
Battery (sealed lead acid,
maintenance free)
w Standard
w Additional modules possible
(up to 4 EXB)
Environment
w Operating temperature range
w Storage temperature range
w Relative humidity
w Noise level
(1) The high and low thresholds can be adjusted using Personal Solution-Pac software.
(2) Up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software.
(3) Adjustable to 100 V (10% derating of output power) 120 V / 127 V.
(4) Battery Evolution S EXB 1250/1750: 2 strings, each 4 x 12 V / 9 Ah.
(5) Battery Evolution S EXB 2500/3000: 2 strings, each 6 x 12 V / 9 Ah.
This product is designed for IT power distribution system.
All manuals and user guides at all-guides.com
Evolution S
Evolution S
1250
1750
1250VA/1150W
1750VA/1600W
47 Hz to 70 Hz, 56.5 Hz to 70 Hz (60 Hz system)
4 x 12 V
7.2 Ah
Evolution S EXB 1250/1750
< 45 dBA
Evolution
2000
2000VA/1600W
Single phase 120 V
89 V to 151 V
(1)
120 V (+6/-10%)
(3)
50/60 Hz ±0.1%
4 x 12 V – 9 Ah
No
(4)
0 to 40ºC
-20ºC to 50ºC
20 to 90% (without condensation)

6. Appendices

Evolution S
Evolution S
2500
3000
2500VA/2250W
2880VA/2700 W
(2)
6 x 12 V
6 x 12 V
7.2 Ah
9 Ah
Evolution EXB S 2500/3000
< 50 dBA
86-81710-00EN A03 - Page 25
(5)

Publicité

Table des Matières

Dépannage

loading

Table des Matières