Appendices; Technical Specifications - Eaton Pulsar Série Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour Pulsar Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6.1

Technical Specifications

Evolution
Output power
AC input power
w Rated input voltage
w Input-voltage range
w 50 Hz input-frequency range
w 60 Hz input-frequency range
Output on battery power
w Voltage
w Frequency
Battery (sealed lead acid,
maintenance free)
w Tower model
w Rack model
Environment
w Operating temperature
range
w Storaage temperature range
w Humidity
w Noise Level
(1) The high and low thresholds can be adjusted using Personal Solution-Pac software.
(2) Up to 40 Hz in extended frequency mode (programmable using Personal Solution-Pac software).
(3) Adjustable to 100 V (10% derating of output power) 120 V / 127 V.
This product is designed for IT power distribution system.
650 / 650 Rack
850 / 850 Rack
650 VA /
850 VA /
420 W
600 W
1 x 12 V -9 Ah
2 x 12 V -7.2 Ah
2 x 6 V -9 Ah
4 x 6 V -7.2 Ah
0 to 35ºC
20 to 90% (without condensation)
1150 / 1150 Rack
1150 VA /
770 W
Single phase 120 V
89 V to 151 V
(1)
47 Hz to 70 Hz
(2)
56.5 Hz to 70 Hz
(2)
120 V (+6% / -10%)
(3)
50/60 Hz ±0.1 Hz
2 x 12 V -9 Ah
4 x 6 V -9 Ah
-20ºC to 50ºC
< 40 dbA

6. Appendices

1550 / 1550 Rack
1550 VA /
1100 W
3 x 12 V -9 Ah
6 x 6 V -9 Ah
0 to 40ºC
86-81700-00EN A02 - Page 25