Important - Canadian Spa Halifax Manuel D'instructions

Masquer les pouces Voir aussi pour Halifax:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Electrical Installation 50 Hz (U.K. / Europe)
Spa Model
Halifax
Montreal
Alberta
Kingston
Niagara
St Lawrence 13' Sport Pool
St Lawrence 16' Swim Spa
St Lawrence 20' Swim Spa
Ottawa
IMPORTANT: The electrical wiring of this spa must meet the
requirements of any applicable local codes. The electrical circuit
must be installed by a qualified electrician and approved by a local
building/electrical inspection authority.
1. This spa must be permanently connected (hard wired) to the
power supply. No plug-in connections or extension cords are to
be used in conjunction with the operation of the spa.
Supplying power to the spa which is not in accordance with
these instructions will void both the independent testing agency
listing and the manufacturer's warranty.
2. The power supplied to this spa must be a dedicated circuit with
no other appliances or lights sharing the power provided by the
circuit.
3. To determine the proper wire size, see Electrical Requirements
section.
a) Wire size must be appropriate as per local codes.
b) All wiring must be copper to ensure proper connections. Do
not use aluminum wire. Using aluminum wire will void the
manufacturer's warranty.
4. Although not required, a suitably rated isolator switch is
recommended for accessibility.
5. The electrical circuit supplied for the spa must include a suitable
Ground Fault (RCD) having a rated residual operating
current not exceeding 30 mA.
IMPORTANT: For supply connections, use conductors sized on the
basis of amperage but rated for 75°C (167°F).
6. An RCD breaker must be used in order for the spa to function
properly.
7. To gain access to the spa's power terminal block, remove the
screws to the access panel located under the Topside Console.
Remove the cover to the spa controller.
8. Feed the supply power cable through the side of the spa or from
underneath the unit. Use the appropriate cable gland to secure
the power supply.
9 Connect the wires, colour to colour on the terminal block.
TIGHTEN SECURELY (all wires must be connected securely or
damage could result).
10. After connecting your the electrical connection close the spa
control box cover and replace the spa access panels.
Installation: Electrical requirements
Voltage requirement
220V
220V
220V
220V
220V
220V
220V
220V
220V
Minimum RCD Size
13A
32A
50A
50A
50A
60A
60A
60A + 50A
50A
ELECTRICAL WIRING PLAN (UK)
Refer to this table for the electrical requirements of your Canadian Spa hot tub.
Do not use an electrical
extension cord to install any Canadian Spa hot tub.
The RCD (ground fault circuit interrupter) must be installed according to the
diagrams below.
1. Consumer Panel
(RCD Protected)
Canadian Spa Company requires that the electrical installation of your
hot tub is carried out by a professionally licensed electrician and that
all local electrical and building codes are adhered to.
Access to the electrical pack can be found by removing the panel
directly below the topside control.
CONNECTING HOT TUB TO RCD AND MAIN PANEL:
• All hot tubs must be wired with the appropriate sized wiring.
Failure to do so will cause equipment damage and will not be
covered by your warranty
• All hot tubs must be protected with a appropriately sized RCD
in the consumer panel. Have your electrician verify using
the diagram below
ITEMS NEEDED TO HELP COMPLETE ELECTRICAL CONNECTION:
RCD Breaker, electrical cable (check length and width for amperage
and distance), cable gland, clips.
10
N/A
6 mm
6 mm
6 mm
RCD Breaker
6 mm
6 mm
Hot tub control
6 mm
6 mm
6 mm
3. Hot tub Control box
2. Outside isolation
switch
Consumer

Publicité

Table des Matières
loading

Table des Matières