Mounting distance for panelled wall - combustible material
Fermacel 13
With convection above and below the stove
Convection area above the stove:
min 400 cm² (may be distributed).
Upper point of convection holes must
be min. 200 mm from combustible
material.
A
Convection area below the stove:
min. 300 cm² (may be distributed)
Distance to combustible material
min.
38
B
B
A-A
400
Min.
mm
250
mm (e.g side wall)
RAIS - manual for RAIS 900
NB!!
Insulated chimney
down to the smoke
connector.
(not included)
A
100
Min.
mm
400
Min.
mm
B-B
To guide the hot air out of the
gratings, install a non-combustible
plate with 30 mm fire batt on,
just above the holes.
Distance
375
min.
Distance to furniture
900
min.
mm
Convection hole below the
stove must be knocked out !!
mm