Commissioning
 Verify that all components have been properly mounted and electrically
connected.
6.1
Entering the tank data
 Verify that zero calibration has been performed.
6.1.1
Adjusting the tank shape
Verify that the arrow at the bottom of the display points to the unit Litres.
The display shows the code of the selected tank shape.
- When the unit is commissioned for the first time, the displayed code
is 0. Code 0 means that no tank shape has yet been selected.
1. Use the two programming keys to set the code of the tank shape deter-
mined (see chapter "Tank shape").
2. Press the function key to confirm the setting.
6.1.2
Tank volume
Verify that the arrow at the bottom of the display points to the unit m³.
The display shows the tank volume set.
- The value 0000 means that no tank volume has yet been entered.
1. Use the programming keys to enter the total volume of the tank facility
determined.
2. Press the programming key (arrow up) to select the digit to be changed.
3. Then press the programming key (arrow down) to change the value of
the selected digit.
- Up to a value of 9999 litres, the value is entered in litres without a dec-
imal place.
- In the case of volumes > 9999 litres, the value is entered in cubic
metres (1000 litres = 1 cubic metre) with a decimal place.
4. Use the programming key (arrow up) to move the decimal place.
5. Press the function key to confirm the setting.
Commissioning
EN
21