VDD.. – Roof Fans
3.2

Dimensions

Series VDD.. 315-710
D
D
F
C
F
C
Y
Y
LK
B
A
LK
B
A
All dimensions in mm
3.3

Electrical connection

m WARNING
The fan must be isolated from the mains power supply and secure against being switched on again before
all maintenance and installation work or before opening the terminal compartment!
– The electrical connection and start-up must only be carried out by qualified electricians according to the information
in the terminal box / isolator switch and the attached wiring diagrams.
– All relevant standards, safety regulations (e.g. DIN VDE 0100), as well as the technical connection conditions of
energy suppliers are to be adhered to!
– Network configuration, voltage and frequency must be consistent with the rating plate information.
– In principle, the motors are wired in the clockwise field of rotation for clockwise rotation.
– Protective conductors, including additional equipotential bonding, must be properly installed!
– Check the waterproofing of the connection cable and tight clamping of the strands.
– The insertion of the supply line must be carried out by specialists! The connection line in the terminal box/ isolator
switch (IP 65) must compensate for the potential fan vibrations.
Installation accessories for the terminal box/isolator switch must meet the requirements of IP 65.
Never lay cables over sharp edges!
3.4

Commissioning

m WARNING
The rotating impeller can crush fingers.
Ensure protection against contact before commissioning!
The following inspection work must be carried out or checked before commissioning:
– Check designated use of fan
– Check permissible transport media temperature
– Compare power consumption to rating plate data
– Check fan for professional electrical installation
– Check protective conductor connection
– Remove installation residues from the fan or duct
– Check all parts for tightness, particularly screws, nuts, protection guards. Do not loosen screws in the process!
Loose parts must not enter the fan.
– Check fan for solid mounting! The terminal box / isolator switch and motorised impeller unit must be freely acces-
sible.
– Ensure that the suction and outlet areas cannot be accessed by unauthorised persons.
– Check tightness of all connections (if necessary)
– Check free movement and direction of rotation of impeller by briefly switching on; Wear protective glasses when
checking.
– Compare power consumption to rating plate data
– Check fan for vibration and noise during test run. In case of excessive vibration and/or noise, it can be assumed that
the fan is operating outside of its operating range. In this case, contact the manufacturer by all means!
Fig.1
Type
A
B
y
y
580
450
VD 315
VD 355
645
535
VD 400
VD 450
730
590
VD 500
VD 560
925
750
VD 630
VD 710 1260 1050
5
Ø C
D
E
F
H
y
605
570
740
640
30
765
690
12
860
760
136
965
790
1070
1015 605
40
1155
1070 674
14
1365
65
1130 751
EN
electr.
connec-
Ø LK
Y
tion
X
356
8 x
M8
395
438
487
6 x
M8
541
8 x
M10